Download Print this page

Sealey SDH102 Manual page 3

Advertisement

Carefully slide the water tank forward making sure no spillage occurs.
Before replacing water tank dry it off thoroughly and also remove any mildew deposits.
4.1.5.
Continuous drainage:
4.1.5.1.
Connect a water pipe (not supplied) to the drain on the rear of the unit. The water pipe requires an inner diameter of 9mm and should
not be longer than 1.5 metres. ensure the connection does not leak.
WArNiNG! The water pipe must AlWAYS be lower along all of it's length than the unit outlet drain height.
5.
r 290 refriGerANt WArNiNGS
5.1.
iNStAllAtiON, SerViCe ANd rePAir Of APPliANCeS CONtAiNiNG r 290
WArNiNG! To avoid damage place the unit in an upright position at least 24 hours before installation.
WArNiNG! make sure the air outlet and air inlet are never blocked.
WArNiNG! only operate on a level surface to make sure no water leaks out.
dO NOt exceed impedance greater than 0.236 ohm in supply the appliance is connected to. Failure to comply may lead the supply
8
authority to impose restrictions to connection. Please consult your energy supply authority if the use of equipment exceeds 0.236 ohm.
Any person who is involved with working on or breaking into a refrigerant a refrigerant circuit should hold a current valid certificate from
9
an industry-accredited assessment authority, which authorises their competence to handle refrigerants safety in accordance with an
industry recognized assessment specification.
Remember the environment when disposing of packaging around the appliance and when the appliance has reached the end of its life.
9
The appliance shall be stored in a well-ventilated area where the size corresponds to the room area as specified for operation.
9
Operate the unit in a well ventilated area where the size corresponds to the room area as specified for operation.
Store in an area where mechanical damage can not occur. Use care when storing the appliance to prevent mechanical faults.
9
5.1.1.
information concerning refrigerant pipes
5.1.1.1.
The installation of pipe-work shall be kept to a minimum.
5.1.1.2. Pipe-work shall be protected from physical damage and, in the case of flammable refrigerants, shall not be installed in an
unventilated space.
5.1.1.3.
Compliance with national gas regulations shall be observed.
5.1.1.4.
mechanical connections shall be accessible for maintenance purposes.
5.1.1.5. Appliances containing flammable refrigerants, the minimum floor area of the room shall be mentioned in the form of a table or a single
figure without reference to a formula.
WArNiNG! Servicing shall be performed only as recommended by the manufacturer.
WArNiNG! ducts connected to an appliance shall not contain a potential ignition source.
When the dehumidifier is turned on, the fan can work continuously under normal conditions to provide the minimum air volume of
9
100m³/h even when the compressor is closed due to the temperature controller.
dO NOt pierce or burn.
8
Use only implements recommended by the manufacturer for defrosting or cleaning.
9
dO NOt perforate any of the components in the refrigerant circuit. Refrigerant gas may be odourless.
8
only persons authorized by an accredited agency certifying their competence to handle refrigerants in compliance with sector
9
legislation should work on refrigerant circuit.
All repairs must be carried out in accordance with the manufacturer's recommendations.
9
Maintenance and repairs requiring the assistance of other qualified personnel must be carried out under the supervision of specialists
9
in the use of inflammable refrigerants.
dO NOt perforate any of the components in the refrigerant circuit. Refrigerant gas may be odourless.
8
5.1.2.
Checks to the area
5.1.2.1. Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is
minimised. For repair to the refrigerating system, the following precaution shall be completed prior to conducting work on the system.
5.1.3.
Work procedure
5.1.3.1. Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while
the work is being performed.
General work area
5.1.4.
5.1.4.1. All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined
spaces shall be avoided.
5.1.5.
Checking for presence of refrigerant
5.1.5.1.
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of
potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
5.1.6.
Presence of fire extinguisher
5.1.6.1. If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment
shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
5.1.7.
No ignition sources
5.1.7.1.
no person carrying out work in relation to a refrigerating system which involves exposing any pipe work shall use any sources of
ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant
can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to
make sure that there are no flammable hazards or ignition risks. "No Smoking" signs shall be displayed.
5.1.8.
Ventilated area
5.1.8.1.
ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A
degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
5.1.9.
Checks to the refrigerating equipment
5.1.9.1. Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the
manufacturer's maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer's technical department for
assistance.
© Jack Sealey limited
Original Language Version
SdH102 Issue 1 07/11/18

Advertisement

loading