Application Options - LG MULTI V HYDRO KIT ARNH963K2A4 Installation Manual

Medium temperature
Table of Contents

Advertisement

The water circuit guidelines and diagrams are for illustrative purposes and are to be used for references only; not all components and accessories
local, state, and federal codes.

Application Options

Water Tank (Domestic Hot Water) + Floor Heating (Factory Default Setting)
Figure 25: Water Tank (Domestic Hot Water) + Floor Heating System Schematic.
Wi-Fi Module
LG
Field Supplied
Supplied
Balancing
Valve with
Flow Meter
Automatic Air
Separator
Hydro Kit
Water Pump
Strainer
Drain
• Verify that Hydro Kit PCB DIP Switch Group 2 is set correctly for water tank (domestic hot water) + floor heating installation applications
(this application is the factory default setting). (Refer to the Hydro Kit DIP Switch Settings pages in the Pre-Commissioning section.)
• The domestic hot water tank is for hot water applications and uses the indirect heat exchange method for heating;
freeze like ethylene glycol to its water.
• For sensing air temperature at a specific area, choose a remote temperature sensor or a wired remote controller, depending on the Hydro
Kit PCB DIP Switch Group 3 setting. (Refer to the Hydro Kit PCB DIP Switch Settings pages in the Pre-Commissioning section.)
• When installing a floor heating system, to measure room temperature, use the Hydro Kit controller or a remote temperature sensor (sold
separately).
• See the Indirect Water Storage Tank Sensor Well and Sensor Installation information. To prevent condensation from forming in floor cooling
applications, set minimum / maximum cooling temperatures.
• For three-way valve and / or two-way valve control, see the Wiring section.
Table 17: Three-Way Valve and Two-Way Valve Control Application.
Mode
Fan Coil Unit - Not Use
Cooling
Priority - Water Tank (Domestic Hot Water)
Heating
Priority - Floor Heating
INSTALLING THE WATER CIRCUIT
Relief Valve
Meter Check
Shut-Off
Valve
Valve
Service Port
Shut-Off
Valve
Service Port
Shut-Off
Valve
Magnetic Dirt
Separator
Description
Fan Coil Unit - Use
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Remote
Temperature
Water Tank
Temperature
Hot
Water
Tank
Fan Coil Unit
Shut-Off
Valve
Water Supply
Water Supply
Three-Way Valve Operation
Floor Heating
Floor Heating
Water Tank (Domestic Hot Water)
Floor Heating
Application Options
Wired Remote
Controller
• When selecting a water tank,
ALWAYS use an INDIRECT tank
where the Hydro Kit water circuit
is isolated from the domestic
water system. Failure to follow
instructions will result in product
malfunction.
• The heating operation mode of
the water tank (domestic hot
water) is not a mode selection
using the remote controller. The
heating operation mode switches
Floor Heating
the three-way valve operation to
the water tank operation based
on the water tank temperature.
• It is impossible to operate water
tank (domestic hot water) during
cooling mode.
Two-Way Valve Operation
Open
Close
No Control
No Control
do not add anti-
43