Connecting

Safety instructions
Risk of death due to hazardous voltage!
Before starting work, disconnect the system and the device from the power supply.
Risk of death due to electric shock and arc flashover!
For the 5 A device, it is only possible to measure the current via external current
transformers. When using the current transformers, the circuit is not protected by a fuse.
• Switch off and lock out all power supplying this equipment before working on the device.
• Never open the secondary circuit of the current transformer under load.
• Short-circuit the secondary current terminals of the current transformer before removing
• Always follow the safety instructions for the current transformers used.
Possible risk of death due to damaged device!
Using devices when they are damaged may result in death, serious injury, or property
damage.
• Do not install damaged devices.
• Never start up damaged devices.
NOTICE
Equipment damage due to lack of fusing
Non-fused voltage measuring inputs may lead to device and equipment damage.
Always protect the device with an IEC approved fuse or with an IEC approved miniature
circuit breaker.
7KT multimeter
Manual, 08/2018, 2514284149-01
DANGER
DANGER
this device.
WARNING
5
41