Figure 2-1 Example: Direct Grounding Of Afd4 / Afd4 (Fm) - Siemens SIMATIC AFD4 Product Information

Bus links active field distributors
Table of Contents

Advertisement

Direct grounding
The shielding of the bus lines is grounded directly in the hazardous area and in the safe
area. This is possible if the equipotential bonding PA runs from the FDC 157 couplers (in the
safe area) to the field devices (in hazardous areas), which means if a corresponding
equipotential bonding conductor is installed.
Note
Direct grounding
The braided shielding of the connection cables must be guided under the shielding clamps of
the active field distributors.
Example: Direct grounding of AFD4 / AFD4 (FM)
Figure 2-1
Example: Direct grounding of AFD4 / AFD4 (FM)
Active field distributors AFD4, AFD4 (FM), AFD8 and AFS
Product Information, 02/2015, A5E03775304-AC
2.2 Grounding AFD4 / AFD4 (FM) / AFD8 and AFS
Installing and connecting
13