Figure 2-3
IP30 cover for AFD4 / AFD4 (FM) / AFD8
The connections of the main cables inside the enclosure of the AFD4 / AFD4 (FM) / AFD8
are sealed with an IP30 cover. Opening the IP30 cover switches off the voltage supply to the
terminals and the feed lines.
In the hazardous area Zone 2, you are permitted to open the IP30 cover during operation for
visual inspection.
NOTICE
IP30-Cover with AFS
Despite the IP30 cover, the requirements for Zone 2 are not met because the AFS is
always connected directly to the FDC 157 coupler.
Zone 2: Disconnecting the main line / connecting the main line to AFD4 / AFD4 (FM) / AFD8
Explosion hazard
In hazardous area Zone 2, you are not permitted to disconnect the main line from an AFD4
/ AFD4 (FM) / AFD8 during operation if it is connected directly to an FDC 157 coupler or an
AFS.
Before you start the work, disconnect the voltage supply to the FDC 157 coupler(s).
In hazardous area Zone 2, you are permitted to disconnect a main line from an AFD4 / AFD4
(FM) / AFD8 during operation if it connects two AFD4 / AFD4 (FM) / AFD8.
Active field distributors AFD4, AFD4 (FM), AFD8 and AFS
Product Information, 02/2015, A5E03775304-AC