7.2

Address zones with RMZ operator units

7.2.1
RM... controllers
For the Synco 700 RM... controllers, the zone addresses can be set with the
RMZ790 and RMZ791 operator units. The zone addresses can be set without
commissioning tool, also referred to as "Easy configuration".
Access at the Password level
To set the zone address, use the following path to the "Room" operating page:
This is where the geographical zone is set.
Main menu > Commissioning > Communication > Room
Room
Geogr zone (ap):
Time switch op:
Autonomous
TS slave (apartm):
7.2.2

QAW740 room unit

The QAW740 room unit only contains the "Geographical zone (apartment)". The
zone address can be set via the operator controls on the front of the unit.
Step
Action
1
To access the setting mode, press the presence button
for ca. 6 seconds. Letter A is displayed and the zone
address can be set.
2
Set the zone address with the rotary knob.
In this example, the value is 5, thus A 5
Note: A stands for "Geographical zone (Apartment)"
3
Briefly press the presence button again to go to other
settings (to set values with rotary knob, see Step 2).
4
After setting the zone address, press the presence button
to exit setting mode.
Zone addresses in the range 1...126 can be set for the "Geographical zone
(apartment)" in the QAW740 room unit.
KNX bus communications
Communication via zone addresses
opens the operating pages and operating lines.