Safety Instructions For Motor Reactors - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor-side power components
7.1 Blocksize
7.1.1.2

Safety instructions for motor reactors

Fire through overheating due to insufficient ventilation clearances
Insufficient ventilation clearances can result in overheating with danger to persons as a
result of smoke and fire. This can also result in increased downtime and reduced service
lives for devices/systems.
• It is essential that you maintain 100 mm ventilation clearances above and below the
Burns resulting from high surface temperature of the motor reactor
The motor reactors can become very hot. You can be severely burnt when touching the
surface.
• Mount the motor reactors so that they cannot be touched. If this is not possible, at the
NOTICE
Damage to the motor reactors due to use of non-approved components
If components are used that have not been approved, damage or malfunctions can occur in
the devices or the system itself. There is a risk that the motor reactor will be thermally
damaged.
• Use only motor reactors that have been approved for SINAMICS by Siemens.
NOTICE
Damage to the motor reactor if the maximum output frequency is exceeded
The maximum permissible output frequency when motor reactors are used is 150 Hz. At a
higher output frequency, the motor reactor may be damaged.
• Do not operate the motor reactors above the maximum permissible output frequency of
NOTICE
Damage to the motor reactor if the maximum pulse frequency is exceeded
The maximum permissible pulse frequency when using motor reactors is 4 kHz. At a higher
pulse frequency, the motor reactor may be damaged.
• Do not operate the motor reactors on the Power Module above the maximum
190
WARNING
component.
CAUTION
dangerous locations, attach an appropriate warning note that is clearly visible and easy
to understand.
150 Hz.
permissible pulse frequency of 4 kHz.
Manual, 06/2019, 6SL3097-5AL00-0BP1
AC Drive

Advertisement

Table of Contents
loading

Table of Contents