Huawei PowerCube 500 User Manual page 50

Hide thumbs Also See for PowerCube 500:
Table of Contents

Advertisement

PowerCube 500 (CPS300-N18A1H)
User Manual
Indicator
Status
Issue 02 (2019-08-30)
Alarm Name
Possible Cause
Discharge
The battery
High
temperature is too
Temperature
high.
Protection
The device is
faulty.
Charge High
The battery
Temperature
temperature is too
Protection
high.
The device is
faulty.
Overcharge
The battery voltage
Protection
is too high.
The device is
faulty.
Copyright © Huawei Technologies Co., Ltd.
5 Alarms and Troubleshooting
Solution
technical support.
1. Check whether the
temperature control device
such as the fan or air
conditioner in the battery
compartment is abnormal.
If yes, maintain the
temperature control
device.
If no, go to the next step.
2. Reset the ESMU and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
1. Check whether the
temperature control device
such as the fan or air
conditioner in the battery
compartment is abnormal.
If yes, maintain the
temperature control
device.
If no, go to the next step.
2. Reset the ESMU and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei
technical support.
1. Handle function module
alarms and check whether the
alarm is cleared.
If yes, no further action is
required.
If no, go to the next step.
2. Charge the battery and check
whether the alarm is cleared
and battery backup time is
normal.
If yes, no further action is
required.
If no, go to the next step.
3. Replace the battery and
44

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cps300-n18a1h

Table of Contents