TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E
TZIDC-120 with Ex nA IIC T6 or T4 Gc marking
Current circuit (terminal)
Signal circuit
(+11 / −12)
Mechanical digital feedback
(Limit1: +51 / −52)
(Limit2: +41 / −42)
Special conditions
•
Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
installation location (manufacturer's declaration or
certificate from an inspection authority).
•
For the 'digital feedback with proximity switches' circuit,
external measures must be implemented to prevent the
rated voltage from being exceeded by more than 40 % in the
event of transient disturbances
•
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a potentially hazardous atmosphere would be
present in zone 2 at the same time that installation or
maintenance or repair work was being carried out.
•
Only non-flammable gases may be used for the pneumatic
power supply
•
Only suited cable entries must be used that meet the
requirements of EN 60079-15.
System bus, computer interfaces
U = 9 to 32 V DC
I = 11.5 mA
U = 5 to 11 V DC
FM / CSA
CSA International
Certificate
Certificate
Class 2258 04
Class 2258 02
Electric data
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
For use in
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
Terminals 51 / 52
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient temperature
Note
•
The 'x' in P/N denotes minor mechanical variations or
optional features.
•
Local communication interface (LCI) shall not be used in a
hazardous location.
•
Each pair of conductors of each intrinsic safety circuit shall
be shielded.
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For
Hazardous Locations
PROCESS CONTROL EQUIPMENT – For
Hazardous Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X
32 V DC; max.15 mA
(powered by a SELV circuit)
U max = 24 V
C
= 2.8 nF
i
I max = 250 mA
L
= 7.2 uH
i
U max = 30 V
C
= 3.8 nF
i
I max = 50 mA
L
= 0 uH
i
U max = 16 V
C
= 60 nF
i
I max = 20 mA
L
= 100 uH
i
U max = 16 V
C
= 60 nF
i
I max = 20 mA
L
= 100 uH
i
21
T4
85 °C