Fm / Csa - ABB TZIDC Commissioning Instruction

Digital positioner
Hide thumbs Also See for TZIDC:
Table of Contents

Advertisement

TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E
TZIDC-120 with Ex nA IIC T6 or T4 Gc marking
Current circuit (terminal)
Signal circuit
(+11 / −12)
Mechanical digital feedback
(Limit1: +51 / −52)
(Limit2: +41 / −42)
Special conditions
Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
installation location (manufacturer's declaration or
certificate from an inspection authority).
For the 'digital feedback with proximity switches' circuit,
external measures must be implemented to prevent the
rated voltage from being exceeded by more than 40 % in the
event of transient disturbances
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a potentially hazardous atmosphere would be
present in zone 2 at the same time that installation or
maintenance or repair work was being carried out.
Only non-flammable gases may be used for the pneumatic
power supply
Only suited cable entries must be used that meet the
requirements of EN 60079-15.
System bus, computer interfaces
U = 9 to 32 V DC
I = 11.5 mA
U = 5 to 11 V DC

FM / CSA

CSA International
Certificate
Certificate
Class 2258 04
Class 2258 02
Electric data
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
For use in
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
Terminals 51 / 52
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient temperature
Note
The 'x' in P/N denotes minor mechanical variations or
optional features.
Local communication interface (LCI) shall not be used in a
hazardous location.
Each pair of conductors of each intrinsic safety circuit shall
be shielded.
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For
Hazardous Locations
PROCESS CONTROL EQUIPMENT – For
Hazardous Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X
32 V DC; max.15 mA
(powered by a SELV circuit)
U max = 24 V
C
= 2.8 nF
i
I max = 250 mA
L
= 7.2 uH
i
U max = 30 V
C
= 3.8 nF
i
I max = 50 mA
L
= 0 uH
i
U max = 16 V
C
= 60 nF
i
I max = 20 mA
L
= 100 uH
i
U max = 16 V
C
= 60 nF
i
I max = 20 mA
L
= 100 uH
i
21
T4
85 °C