Annex B - Valid Unit Configurations - Siemens DF8000 Installation Function & Configuration Commissioning Safety Regulations

Input / output multiplexing system
Table of Contents

Advertisement

11
Annex B – Valid unit configurations
36
Building Technologies
Fire Safety & Security Products
The following table illustrates the valid configurations for I/O units based on a
DF8003 CPU. Note that you cannot mix supervised modules (DF8045 and
DF8046) with on/off modules (DF8020 and DF8040) on the same CPU. Instead,
different units can coexist on the same RS485 bus until the address limit is
reached: 16 single units (1 to 3 I/O modules) or 8 double units (4 to 6 I/O modules).
I/O configuration:
Input only:
48 in (double)
40 in (double)
32 in (double)
24 in (single)
16 in (single)
8 in (single)
Output only:
48 out (double)
40 out (double)
32 out (double)
24 out (single)
16 out (single)
8 out (single)
Input and output:
40 in / 8 out (double)
32 in / 8 out (double)
24 in / 8 out (double)
16 in / 8 out (single)
8 in / 8 out (single)
32 in/16 out (double)
24 in/16 out (double)
16 in/16 out (double)
8 in / 16 out (double)
24 in/24 out (double)
16 in/24 out (double)
8 in/24 out (double)
16 in/32 out (double)
8 in/32 out (double)
8 in/40 out (double)
Supervised input:
24 in (double)
20 in (double)
16 in (double)
12 in (single)
8 in (single)
4 in (single)
Tab.23. Valid configurations of DF8000 units
Modules:
1 x DF8003 plus:
6 x DF8040
5 x DF8040
4 x DF8040
3 x DF8040
2 x DF8040
1 x DF8040
1 x DF8003 plus:
6 x DF8020
5 x DF8020
4 x DF8020
3 x DF8020
2 x DF8020
1 x DF8020
1 x DF8003 plus:
5 x DF8040 + 1 x DF8020
4 x DF8040 + 1 x DF8020
3 x DF8040 + 1 x DF8020
2 x DF8040 + 1 x DF8020
1 x DF8040 + 1 x DF8020
4 x DF8040 + 2 x DF8020
3 x DF8040 + 2 x DF8020
2 x DF8040 + 2 x DF8020
1 x DF8040 + 2 x DF8020
3 x DF8040 + 3 x DF8020
2 x DF8040 + 3 x DF8020
1 x DF8040 + 3 x DF8020
2 x DF8040 + 4 x DF8020
1 x DF8040 + 4 x DF8020
1 x DF8040 + 5 x DF8020
1 x DF8003 plus:
6 x DF8045 or DF8046
5 x DF8045 or DF8046
4 x DF8045 or DF8046
3 x DF8045 or DF8046
2 x DF8045 or DF8046
1 x DF8045 or DF8046