2 Explanation of the Blocks
2.4 FB20 "Parameter_Access"
Error list
The FB 20 "Parameter_Access" can output the following error codes in the
"errorID" parameter:
Table 2-10: Error codes in "errorID" parameter
Error number
0
8000
8001
8002
8003
8004
8005
SINAMICS S120 at S7-300/400F
Entry-ID: 68624711,
V1.1,
Description
No error
DB_No_send and DB_No_rev
are identical.
DB_No_rev or DB_No_send is
zero.
SFC53 "WEREC" outputs
errors
SFC52 "RDREC" outputs
errors
The SFC24 "TEST_DB"
reports:
Send DB is empty (length 0),
non-existent or faulty.
The SFC24 "TEST_DB"
reports:
Receive DB is empty (length
0), non-existent or faulty.
12/2014
Note
Check the parameters of FB 20
"Parameter_Access".
In the instance DB of FB20, the error
code of the SFC53 is stored in
#WD_REC_STATUS.
In the instance DB of FB20, the error
code of the SFC52 is stored in
#RD_REC_STATUS.
In the instance DB of FB20, the error
code of the SFC24 is stored in
#TEST_DB_1_STATUS. If it is 0, the
DB is empty or write protected.
In the instance DB of FB20, the error
code of the SFC24 is stored in
#TEST_DB_2_STATUS. If it is 0, the
DB is empty or write protected.