Test Values (Brake And Motor); Brake Voltage; Motor Voltage; Winding Resistance - ABB PME120-AI Service Instruction

Electrical rotary actuator
Hide thumbs Also See for PME120-AI:
Table of Contents

Advertisement

26
PME120-AI / PME120-AN (Contrac) ELECTRICAL ROTARY ACTUATOR | SEI/PME120-EN REV. A
... 8 Electrical test values

Test values (Brake and Motor)

Brake voltage

DC 135 V with AC 115/AC230 V mains supply.

Motor voltage

Check for currents symmetry (i. e. with clip-on ammeter).

Winding resistance

Depending on the actuator version proceed as follows:
PME120-AI (integrated electronic unit)
A Mains fuse
B Spare fuse
C Heater fuse
(only for 25 °C Version)
Figure 36: Pin assignment
1. Remove the plug.
2. Remove the actuator hood with electronics.
3. Check pins at pin carrier,Refer to pin carrier in Figure 36.
Measuring points
Winding resistance ±5 % at 20 °C (motor); pin. 6-7 / 7-8 / 6-8
Winding resistance ±5 % at 20 °C (brake); terminal 9-10
D Fuse against active feed at 20 mA
setpoint input
Resistance
PME120-AN (separate electronic unit)
1. Remove plug.
2. Measure between pins at actuator plug, see Electronic unit
EAN823 (Contrac) for PME120-AN on page 18 and Electronic
unit EAS822 (Contrac) for PME120-AN on page 20 for pin
reference.
Measuring points
Winding resistance ± 5 % at 20 °C (motor); pin. 1-2 / 2-3 / 1-3
Winding resistance ± 5 % at 20 °C (brake); terminal 9-10
3.4 Ω
50 Ω
Resistance
3.4 Ω
50 Ω