Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Section 1 1MRS757261 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
IEC 61850 point list manual, operation manual and technical manual. 1.3.2 Document revision history Document revision/date Product version History A/2011-05-04 First release B/2011-11-03 1.1.1 Content updated C/2012-03-29 1.1.2 Content updated Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. PML630 Point List Manual...
IEC 61850 Communication Protocol Manual 1MRS757260 Operation Manual 1MRS757183 Technical Manual 1MRS757256 Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation. Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text.
Section 1 1MRS757261 C Introduction To navigate between the options, use • HMI menu paths are presented in bold. Select Main menu/Settings. • LHMI messages are shown in Courier font. To save the changes in non-volatile memory, select Yes and press •...
Page 13
Section 1 1MRS757261 C Introduction Functionality IEC 61850 Binary channel 17-32 B2RBDR Binary channel 33-48 B3RBDR Binary channel 49-64 B4RBDR 1) The function is not used by default. However, it is kept enabled in the Application Configuration tool for instantiation in any additional user defined logic other than the features offered by the IED Connectivity Package.
Section 3 1MRS757261 C Logical node extensions Section 3 Logical node extensions New logical nodes Table 3: New functions in PML630 LN Class Prefix LN Type Description LN Class: 'A' for Automatic control, 'C' for Contingency based, 'LS' for Load shedding) LN Prefix: Contingency based Load shedding (Fast ACLS LSCACLS...
Section 3 1MRS757261 C Logical node extensions 3.1.3 LSCCCLS Table 6: LSCCCLS Attribute name DATA type Explanation M/O/E CCLS class Contingency load shedding (Manual CCLS Data Common Logical node information ABB_c_dINC Mode (Manual load shed function Enable / Disable / Test command / status) ABB_a_dINS Behaviour (Reflects the mode of the...
Section 3 1MRS757261 C Logical node extensions Attribute name DATA type Explanation M/O/E NtwLodInhS ABB_v2_dMV Network load inhibit by system (Load value that is inhibited from being shed by the system) NtwLodMm ABB_v2_dMV Network load mismatch (Total value of non-sheddable loads) NtwShbLod ABB_v2_dMV Network sheddable load (Total value...
Section 3 1MRS757261 C Logical node extensions Extended logical nodes Table 10: Logical nodes included in the IED LN Class Prefix (default) LN Type Description LLN0 General LN0 for LD0 LN0 for Load busbar (load circuit LDLLLN0 breaker and power) information LSLLN0 LN0 for LS commands per busbar SNWLLN0...
Section 3 1MRS757261 C Logical node extensions 3.2.1 LLN0 Table 11: LLN0 Attribute name DATA type Explanation M/O/E LLN0 General LN0 for LD0 Data Common Logical Node Information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate 3.2.2 LDLLN0 Table 12: LDLLN0...
Section 3 1MRS757261 C Logical node extensions 3.2.4 SNWLLN0 Table 14: SNWLLN0 Attribute name DATA type Explanation M/O/E LLN0 LN0 for SubNetwork information Data Common Logical Node Information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate 3.2.5 NCBDLLN0 Table 15: NCBDLLN0...
Section 3 1MRS757261 C Logical node extensions 3.2.7 PWSLLN0 Table 17: PWSLLN0 Attribute name DATA type Explanation M/O/E LN0 for Power source (generator and grid transformer circuit breaker and LLN0 power) information Data Common Logical Node Information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS...
Section 3 1MRS757261 C Logical node extensions Attribute DATA type Explanation M/O/E NamPlt ABB_b_dLPL Name plate Status information ABB_C_dACT Trip 3.2.10 PWSGCSWI Table 20: PWSGCSWI Attribute DATA type Explanation M/O/E CSWI class Power source generator circuit CSWI breaker position Data Common Logical Node Information ABB_c_dINC Mode...
Section 3 1MRS757261 C Logical node extensions 3.2.12 PWSTCSWI Table 22: PWSTCSWI Attribute DATA type Explanation M/O/E CSWI class Power source grid transformer circuit CSWI breaker position Data Common logical node information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Control...
Section 3 1MRS757261 C Logical node extensions 3.2.14 NCBDCSWI Table 24: NCBDCSWI Attribute DATA type Explanation M/O/E CSWI class CSWI Network circuit breaker position Data Common logical node information ABB_c_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Control ABB_b_dDPC Position...
Section 3 1MRS757261 C Logical node extensions Attribute DATA type Explanation M/O/E ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_b_dLPL Name plate Control ABB_b_dDPC Position 3.2.17 LDMMXU Table 27: LDMMXU Attribute DATA type Explanation M/O/E MMXU class MMXU Load feeder circuit breaker power value Data Common logical node information ABB_c_dINC...
Section 3 1MRS757261 C Logical node extensions 3.2.19 DRRDRE Table 29: DRRDRE Attribute DATA type Explanation M/O/E RDRE class RDRE Load Shedding disturbance records Data Common logical node information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Status RcdMade ABB_d_dSPS...
Section 3 1MRS757261 C Logical node extensions 3.2.21 MVGGIO Table 31: MVGGIO Attribute DATA type Explanation M/O/E GGIO class GGIO Generic measured value Data Common logical node information ABB_a_dINC Mode ABB_a_dINS Behaviour Health ABB_c_dINS Health NamPlt ABB_a_dLPL Name plate Status AnIN ABB_a_dMV Measurement Value...
Section 4 1MRS757261 C Glossary Section 4 Glossary Behavior Data extension to IEC 61850-7-4 Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 Logical device zero (0) LHMI Local human-machine interface Logical node...