IEC 60870-5-103 Communication Protocol
Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 630 Series

  • Page 1 ® Relion Protection and Control 630 series IEC 60870-5-103 Communication Protocol Manual...
  • Page 3 Document ID: 1MRS757203 Issued: 2011-02-23 Revision: A Product version: 1.1 © Copyright 2011 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............6 Product documentation set............6 Document revision history.............7 Related documentation..............8 Symbols and conventions..............8 Safety indication symbols..............8 Manual conventions...............8 Section 2 IEC 60870-5-103 overview..........11 IEC 60870-5-103 standard...............11 Communication system principle..........12 Section 3 IEC 60870-5-103 communication engineering....13 IEC 60870-5-103 engineering in PCM600........13 Specific IEC 60870-5-103 settings...........13...
  • Page 8 Table of contents Settings..................22 Supported information types..........22 Function status earth-fault for IEC 60870-5-103 I103EF.....23 Functionality................23 Function block................23 Signals..................23 Settings..................23 Supported information types..........24 Function status fault protection for IEC 60870-5-103 I103FLTPROT................24 Functionality................24 Function block................25 Signals..................25 Settings..................26 Supported information types..........26 IED status for IEC 60870-5-103 I103IED........27 Functionality................27 Function block................28 Signals..................28...
  • Page 9 Table of contents Signals..................34 Settings..................35 Supported information types..........35 Function commands user defined for IEC 60870-5-103 I103USRCMD................35 Functionality................35 Function block................35 Signals..................36 Settings..................36 Supported information types..........36 Function commands generic for IEC 60870-5-103 I103GENCMD................37 Functionality................37 Function block................37 Signals..................37 Settings..................38 Supported information types..........38 IED commands with position and select for IEC 60870-5-103 I103POSCMD............38 Functionality................38 Function block................38...
  • Page 10 Table of contents Generic functions in monitor direction........46 Selection of standard information numbers in control direction..................47 System functions in control direction........47 General commands in control direction........47 Generic functions in control direction........47 Basic application functions............48 Miscellaneous................48 Section 6 Glossary.................51 630 series Communication Protocol Manual...
  • Page 11: Section 1 Introduction

    Section 1 1MRS757203 A Introduction Section 1 Introduction This manual The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation from an IED perspective.
  • Page 12: Product Documentation

    Section 1 1MRS757203 A Introduction Product documentation 1.3.1 Product documentation set Engineering manual Engineering manual Engineering manual Installation manual Installation manual Installation manual Commissioning manual Commissioning manual Commissioning manual Operation manual Operation manual Operation manual Service manual Service manual Service manual Application manual Application manual Application manual...
  • Page 13: Document Revision History

    The service manual is not available yet. 1.3.2 Document revision history Document revision/date Product series version History A/2011-02-23 First release Download the latest documents from the ABB web site http:// www.abb.com/substationautomation. 630 series Communication Protocol Manual...
  • Page 14: Related Documentation

    Section 1 1MRS757203 A Introduction 1.3.3 Related documentation Product-specific point list manuals and other product series- and product-specific manuals can be downloaded from the ABB web site http://www.abb.com/ substationautomation Symbols and conventions 1.4.1 Safety indication symbols The caution icon indicates important information or warning related to the concept discussed in the text.
  • Page 15 Section 1 1MRS757203 A Introduction The function can be enabled and disabled with the Operation setting. • The ^ character in front of an input or output signal name in the function block symbol given for a function, indicates that the user can set an own signal name in PCM600.
  • Page 17: Section 2 Iec 60870-5-103 Overview

    Section 2 1MRS757203 A IEC 60870-5-103 overview Section 2 IEC 60870-5-103 overview IEC 60870-5-103 standard IEC 60870-5-103 is defined as a companion standard for the informative element of protection equipment. While the official IEC 60870-5-103 standard dates back to 1997, the protocol has its roots in the VDEW6 communication protocol from the late 1980’s.
  • Page 18: Communication System Principle

    Section 2 1MRS757203 A IEC 60870-5-103 overview standard. It should also be noticed that these sets of data are mainly defined for a single function protection IED. 630 series IEDs in turn are multifunctional protection and control IEDs whose internal data model is based on the IEC 61850 standard.
  • Page 19: Section 3 Iec 60870-5-103 Communication Engineering

    Section 3 1MRS757203 A IEC 60870-5-103 communication engineering Section 3 IEC 60870-5-103 communication engineering IEC 60870-5-103 engineering in PCM600 The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in PCM600 are used to configure the communication for IEC 60870-5-103 protocol. Add the desired IEC 60870-5-103 function blocks to the application configuration in the Application Configuration tool.
  • Page 20: Settings

    Section 3 1MRS757203 A IEC 60870-5-103 communication engineering Event reporting mode If SeqOfEvent is selected, all GI and spontaneous events will be delivered in the order they were generated by BSW. The most recent value is the latest value delivered. All GI data from a single block will come from the same cycle. If HiPriSpont is selected, spontaneous events will be delivered prior to GI event.
  • Page 21 Section 3 1MRS757203 A IEC 60870-5-103 communication engineering GUID-68284E7B-A24D-4E78-B5BA-736B29F50E9A V1 EN Figure 3: Settings under TIMESYNCHGEN:1 in PST Only CoarseSyncSrc can be set to IEC 60870-5-103, not FineSyncSource. After setting up the time synchronization source, the user must check and modify the IEC 60870-5-103 time synchronization specific settings, under: IED Configuration/Communication/Station communication/IEC60870-5-103:1.
  • Page 23: Section 4 Iec 60870-5-103 Vendor Specific Implementation

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Section 4 IEC 60870-5-103 vendor specific implementation The signal and setting tables specify the information types supported by the IEDs with the communication protocol IEC 60870-5-103 implemented. The information types are supported when corresponding functions are included in the protection and control IED.
  • Page 24: Function Block

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.1.2 Function block I103MEAS BLOCK UL1L2 IEC10000287-1-en.vsd IEC10000287 V1 EN Figure 4: I103MEAS function block 4.1.1.3 Signals Table 4: I103MEAS Input signals Name Type Default Description BLOCK BOOLEAN Block of service value reporting REAL Service value for current phase L1 REAL...
  • Page 25: Supported Information Types

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Name Values (Range) Unit Step Default Description MaxUL1 0.05 - 2000.00 0.05 230.00 Maximum voltage for phase L1 MaxUL2 0.05 - 2000.00 0.05 230.00 Maximum voltage for phase L2 MaxUL3 0.05 - 2000.00 0.05 230.00 Maximum voltage for phase L3...
  • Page 26: Measurands User Defined Signals For Iec 60870-5-103

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.2 Measurands user defined signals for IEC 60870-5-103 I103MEASUSR 4.1.2.1 Functionality I103MEASUSR is a function block with user defined input measurands in monitor direction. These function blocks include the FunctionType parameter for each block in the private range, and the Information number parameter for each block.
  • Page 27: Settings

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.2.4 Settings Table 8: I103MEASUSR Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) InfNo 1 - 255 Information number for measurands (1-255) MaxMeasur1 0.05 -...
  • Page 28: Function Status Auto-Recloser For Iec 60870-5-103 I103Ar

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.3 Function status auto-recloser for IEC 60870-5-103 I103AR 4.1.3.1 Functionality I103AR is a function block with defined functions for autorecloser indications in monitor direction. This block includes the FunctionType parameter, and the information number parameter is defined for each output signal.
  • Page 29: Function Status Earth-Fault For Iec 60870-5-103 I103Ef

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Table 11: I103AR supported indications Info. no. Message Supported Autorecloser active Teleprotection active Protection active CB on by Autorecloser CB ‘on’ by long-time AR Autorecloser blocked 4.1.4 Function status earth-fault for IEC 60870-5-103 I103EF 4.1.4.1 Functionality I103EF is a function block with defined functions for earth fault indications in...
  • Page 30: Supported Information Types

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.4.5 Supported information types Earth fault indications in monitor direction, I103EF Number of instances: 1 Function type is selected with parameter FunctionType. Information number is defined for each output signal. Table 14: I103EF supported indications Info.
  • Page 31: Function Block

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.5.2 Function block I103FLTPROT BLOCK 64_STL1 65_STL2 66_STL3 67_STIN 68_TRGEN 69_TRL1 70_TRL2 71_TRL3 72_TRBKUP 73_SCL 74_FW 75_REV 76_TRANS 77_RECEV 78_ZONE1 79_ZONE2 80_ZONE3 81_ZONE4 82_ZONE5 84_STGEN 85_BFP 86_MTRL1 87_MTRL2 88_MTRL3 89_MTRN 90_IOC 91_IOC 92_IEF 93_IEF...
  • Page 32: Settings

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Name Type Default Description 76_TRANS BOOLEAN Information number 76, signal transmitted 77_RECEV BOOLEAN Information number 77, signal received 78_ZONE1 BOOLEAN Information number 78, zone 1 79_ZONE2 BOOLEAN Information number 79, zone 2 80_ZONE3 BOOLEAN Information number 80, zone 3...
  • Page 33: Ied Status For Iec 60870-5-103 I103Ied

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Table 17: I103FLTPROT supported indications Info. no. Message Supported TYPE Start phase L1 1,7,9 Start phase L2 1,7,9 Start phase L3 1,7,9 Start residual current IN 1,7,9 Trip general Trip phase L1 Trip phase L2 Trip phase L3 Back up trip I>>...
  • Page 34: Function Block

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.6.2 Function block I103IED BLOCK 19_LEDRS 21_TESTM 23_GRP1 24_GRP2 25_GRP3 26_GRP4 IEC10000292-1-en.vsd IEC10000292 V1 EN Figure 9: I103IED function block 4.1.6.3 Signals Table 18: I103IED Input signals Name Type Default Description BLOCK BOOLEAN Block of status reporting...
  • Page 35: Supervison Status For Iec 60870-5-103 I103Superv

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Info. no. Message Supported Local Parameter setting Setting group 1 active Setting group 2 active Setting group 3 active Setting group 4 active 4.1.7 Supervison status for IEC 60870-5-103 I103SUPERV 4.1.7.1 Functionality I103SUPERV is a function block with defined functions for supervision indications in monitor direction.
  • Page 36: Settings

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.7.4 Settings Table 22: I103SUPERV Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) 4.1.7.5 Supported information types Supervision indications in monitor direction, I103SUPERV Number of instances: 1 Function type is selected with parameter FunctionType.
  • Page 37: Function Block

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation GUID-391D4145-B7E6-4174-B3F7-753ADDA4D06F V1 EN Figure 11: I103USRDEF example settings 4.1.8.2 Function block I103USRDEF BLOCK ^INPUT1 ^INPUT2 ^INPUT3 ^INPUT4 ^INPUT5 ^INPUT6 ^INPUT7 ^INPUT8 IEC10000294-1-en.vsd IEC10000294 V1 EN Figure 12: I103USRDEF function block 4.1.8.3 Signals Table 24: I103USRDEF Input signals...
  • Page 38: Settings

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.1.8.4 Settings Table 25: I103USRDEF Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) InfNo_1 1 - 255 Information number for binary input 1 (1-255) InfNo_2 1 - 255...
  • Page 39: Commands In Control Direction

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Commands in control direction 4.2.1 Function commands for IEC 60870-5-103 I103CMD 4.2.1.1 Functionality I103CMD is a command function block in control direction with pre-defined output signals. 4.2.1.2 Function block I103CMD BLOCK 16-AR 17-DIFF 18-PROT...
  • Page 40: Supported Information Types

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.2.1.5 Supported information types Function commands in control direction, pre-defined I103CMD Number of instances: 1 Function type is selected with parameter FunctionType . Information number is defined for each output signals. Info.
  • Page 41: Settings

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.2.2.4 Settings Table 31: I103IEDCMD Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) 4.2.2.5 Supported information types Commands in control direction, I103IEDCMD Number of instances: 1 Function type is selected with parameter FunctionType.
  • Page 42: Signals

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.2.3.3 Signals Table 32: I103USRCMD Input signals Name Type Default Description BLOCK BOOLEAN Block of commands Table 33: I103USRCMD Output signals Name Type Description OUTPUT1 BOOLEAN Command output 1 OUTPUT2 BOOLEAN Command output 2 OUTPUT3 BOOLEAN...
  • Page 43: Function Commands Generic For Iec 60870-5-103 I103Gencmd

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation Function type for each function block instance in private range is selected with parameter FunctionType. Default values are defined in private range 1 - 4. One for each instance. Information number must be selected for each output signal. Default values are 1 - 8. Info.
  • Page 44: Settings

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.2.4.4 Settings Table 37: I103GENCMD Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 127 Function type (1-255) PulseLength 0.000 - 60.000 0.001 0.400 Pulse length InfNo 32 - 239 Information number for command output...
  • Page 45: Signals

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation 4.2.5.3 Signals Table 38: I103POSCMD Input signals Name Type Description BLOCK BOOLEAN Block of indications POSITION INTEGER Position indication of controllable object SELECT BOOLEAN Select indication of controllable object 4.2.5.4 Settings Table 39: I103POSCMD Non group settings (basic) Name...
  • Page 46: Deviations From The Standard

    Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation to the master. A file that has been transferred and acknowledged by the master cannot be transferred again. • The binary signals that are reported by polling are those that are connected to the disturbance function blocks B1RBDR to B6RBDR.
  • Page 47 Section 4 1MRS757203 A IEC 60870-5-103 vendor specific implementation When a new disturbance is recorded by the IED a list of available recorded disturbances (ASDU 23) will be sent to the master, an updated list of available disturbances will also be sent whenever something has happened to disturbances in this list.
  • Page 49: Section 5 Interoperability

    Section 5 1MRS757203 A Interoperability Section 5 Interoperability Physical layer Table 40: Electrical Interface Supported EIA RS-485 number of loads 5.1.1 Optical interface Table 41: Optical interface Supported Glass fibre Plastic fibre F-SMA type connector BFOC/2,5 type connector 5.1.2 Transmission speed Table 42: Transmission speed Supported...
  • Page 50: Common Address Of Asdu

    Section 5 1MRS757203 A Interoperability 5.2.2 Common address of ASDU Table 43: Common address of ASDU Supported One COMMON ADDRESS OF ASDU (identical with station address) More than one COMMON ADDRESS OF ASDU 5.2.3 Selection of standard information numbers in monitor direction 5.2.3.1 System functions in monitor direction...
  • Page 51: Supervision Indications In Monitor Direction

    Section 5 1MRS757203 A Interoperability 5.2.3.3 Supervision indications in monitor direction Table 46: Supervision indications in monitor direction Semantics Supported Measurand supervision I Measurand supervision V Phase sequence supervision Trip circuit supervision I>> back-up operation VT fuse failure Teleprotection disturbed Group warning Group alarm 5.2.3.4...
  • Page 52: Auto-Reclosure Indications In Monitor Direction

    Section 5 1MRS757203 A Interoperability Semantics Supported General start/pick-up Breaker failure 86 to Trip measuring system L to Trip measuring system L Trip measuring system E Trip I> Trip I>> Trip IN> Trip IN>> 5.2.3.6 Auto-reclosure indications in monitor direction Table 49: Auto-reclosure indications in monitor direction Semantics...
  • Page 53: Selection Of Standard Information Numbers In Control Direction

    Section 5 1MRS757203 A Interoperability 5.2.4 Selection of standard information numbers in control direction 5.2.4.1 System functions in control direction Table 52: System functions in control direction Semantics Supported Initiation of general interrogation Time synchronization 5.2.4.2 General commands in control direction Table 53: General commands in control direction Semantics...
  • Page 54: Basic Application Functions

    Section 5 1MRS757203 A Interoperability 5.2.5 Basic application functions Table 55: Basic application functions Supported Test mode Blocking of monitor direction Disturbance data Generic services Private data 5.2.6 Miscellaneous Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in 7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value.
  • Page 55 Section 5 1MRS757203 A Interoperability DRA#-Input IEC103 meaning Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range...
  • Page 57: Section 6 Glossary

    Section 6 1MRS757203 A Glossary Section 6 Glossary ASDU Application-layer service data unit DNP3 A distributed network protocol originally developed by Westronic. The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution. Electromagnetic compatibility Fault number Default function type General interrogation...
  • Page 60 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...