ABB Relion 630 Series Communication Protocol Manual
ABB Relion 630 Series Communication Protocol Manual

ABB Relion 630 Series Communication Protocol Manual

Iec 61850 communication protocol
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

RELION® PROTECTION AND CONTROL
630 series
IEC 61850 Communication Protocol
Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 630 Series

  • Page 1 — RELION® PROTECTION AND CONTROL 630 series IEC 61850 Communication Protocol Manual...
  • Page 3 Document ID: 1MRS756793 Issued: 2019-02-25 Revision: E Product version: 1.3 © Copyright 2019 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............6 Product documentation set............6 Document revision history............. 6 Related documentation..............7 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Functions, codes and symbols............8 Section 2 Introduction to IEC 61850..........13 Related documentation to IEC 61850..........14 Section 3 Substation Configuration description Language (SCL)..
  • Page 8 Table of contents Directional earth fault PDEF............50 Differential protection PDIF............54 Distance protection PDIS............60 Directional overcurrent PDOC............. 99 Overcurrent protection PVOC............103 Rate of change of frequency PFRC...........104 Frequency protection PFRQ............105 Harmonic distortion PHAR............109 Local acceleration logic PLAL........... 109 Motor supervision PMSU............110 Restricted earth fault PNDF............113 Protection scheme PSCH............116...
  • Page 9 Table of contents Logical nodes for generic references..........215 Generic automatic process control GAPC.........215 Generic process I/O GGIO............216 Logical nodes for metering and measurement....... 228 Metering MMTR.................228 Measurement MMXU..............233 Harmonic measurement MHAI..........245 Sequence and imbalance MSQI..........260 Logical nodes for sensors and monitoring........264 Circuit breaker monitoring SCBR..........
  • Page 11: Section 1 Introduction

    Section 1 1MRS756793 E Introduction Section 1 Introduction This manual The communication protocol manual describes a communication protocol supported by the protection relay. The manual concentrates on vendor-specific implementations. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering the communication setup in a substation from a protection relay's perspective.
  • Page 12: Product Documentation

    Commissioning manual GUID-C8721A2B-EEB9-4880-A812-849E1A42B02C V1 EN Figure 1: The intended use of documents during the product life cycle Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product series version...
  • Page 13: Related Documentation

    Section 1 1MRS756793 E Introduction Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Product-specific point list manuals and other product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation. Symbols and conventions 1.4.1...
  • Page 14: Functions, Codes And Symbols

    Section 1 1MRS756793 E Introduction Click Information in the WHMI menu structure. • LHMI messages are shown in Courier font. To save the changes in nonvolatile memory, select Yes and press • Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. •...
  • Page 15 Section 1 1MRS756793 E Introduction Description IEC 61850 IEC 60617 ANSI Transient/intermittent earth-fault INTRPTEF I0> -> IEF 67NIEF protection Admittance-based earth-fault EFPADM Yo> -> 21YN protection Multi-frequency admittance-based MFADPSDE I0> ->Y 67YN earth-fault protection Wattmetric earth-fault protection WPWDE Po> -> Stabilised restricted earth-fault protection LREFPNDF...
  • Page 16 Section 1 1MRS756793 E Introduction Description IEC 61850 IEC 60617 ANSI Negative-sequence overvoltage NSPTOV U2> 47O- protection Residual overvoltage protection ROVPTOV U0> Directional reactive power DQPTUV Q>-->,3U< 32Q,27 undervoltage protection Reverse power/directional DOPPDPR P> 32R/32O overpower protection Underpower protection DUPPDPR P<...
  • Page 17 Section 1 1MRS756793 E Introduction Description IEC 61850 IEC 60617 ANSI Single point control (8 signals) SPC8GGIO Double point indication DPGGIO Single point indication SPGGIO Generic measured value MVGGIO Logic Rotating Switch for function SLGGIO selection and LHMI presentation Selector mini switch VSGGIO Pulse counter for energy metering PCGGIO...
  • Page 18 Section 1 1MRS756793 E Introduction Description IEC 61850 IEC 60617 ANSI Analog channels 1-10 (samples) A1RADR ACH1 ACH1 Analog channels 11-20 (samples) A2RADR ACH2 ACH2 Analog channels 21-30 (calc. val.) A3RADR ACH3 ACH3 Analog channels 31-40 (calc. val.) A4RADR ACH4 ACH4 Binary channels 1-16 B1RBDR...
  • Page 19: Section 2 Introduction To Iec 61850

    Section 2 1MRS756793 E Introduction to IEC 61850 Section 2 Introduction to IEC 61850 The IEC 61850 protocol standard for substation enables the integration of all protection, control, measurement and monitoring functions by one common protocol. It provides the means of high-speed substation applications, station wide interlocking and other functions requiring intercommunication between IEDs.
  • Page 20: Related Documentation To Iec 61850

    Section 2 1MRS756793 E Introduction to IEC 61850 Communication Architecture forum. The Tissues handling is found in www.tissues.iec61850.com. The conformance documents are unique for each product release and refer to each other; the identities included in the related documents refer to a specific version of the IED.
  • Page 21 Section 2 1MRS756793 E Introduction to IEC 61850 Table 2: IEC 61850-related documentation Document ID Title IEC 61850-5 Communication networks and systems in First edition 2003-07 substations - Ref. number: IEC 61850-5:2003(E) Part 5: Communication requirements for functions and devices models IEC 61850-6 Communication networks and systems in First edition 2004-03...
  • Page 23: Section 3 Substation Configuration Description Language (Scl)

    Section 3 1MRS756793 E Substation Configuration description Language (SCL) Section 3 Substation Configuration description Language (SCL) The SCL language is based on XML. However, detailed knowledge of the XML contents is not needed. The SCL XML file (ied.ICD and/or station.SCD) contains five sections, which are specified in IEC 61850–6 clause 9.
  • Page 24: The Substation Section

    Section 3 1MRS756793 E Substation Configuration description Language (SCL) Substation VoltageLevel LNode Communucation Subnetwork Connected AP IED Name AccessPoint Address IED Name AccessPoint Address Services AccessPoint Server Authentication LDevice DataSet Report Control GOOSE Control Inputs SettingControl DataTypeTemplates LNodeType DOType DOType DAType DAType EnumType...
  • Page 25: The Ied Section

    Section 3 1MRS756793 E Substation Configuration description Language (SCL) network with no relation to an existing media and protocol. The mapping to an existing media and protocol is specified in IEC 61850-8-1. The IEC 61850 standard describes in part 7-2 the ACSI in a media and protocol independent form.
  • Page 26 Section 3 1MRS756793 E Substation Configuration description Language (SCL) supported services. The structure of the IED section follows the definitions made in the IEC 61850 standard. Two basic IED types are used in system configuration. • Station level IEDs are located on the station level and are identified as client IEDs when they read or write information from or to the bay IEDs.
  • Page 27 Section 3 1MRS756793 E Substation Configuration description Language (SCL) Subnetwor Server SB1.LD1 Logical Node LLN0 Data LPHD DAXCBR1 DAXSWI1 DAXSWI1 Health Data DASWI2 NamePlt Attribute DAXSWI2 ctlVal DAXSWI3 stVal DAXSWI3 OpCnt DAXSWI4 BlkOpn DAXSWI4 BlkCls Origin ctlModel CBOpCap DAXSWI5 Control PWRMMXU1 IEC09000736_1_en.vsd IEC09000736 V1 EN...
  • Page 28: Tool Concept

    Section 3 1MRS756793 E Substation Configuration description Language (SCL) receiver. The control services are not directly engineered. They are included in the data objects, which handle both directions the command (control) and the response (monitoring). When routing the DO in monitoring direction, the control is also known by the clients.
  • Page 29: Engineering Concept In Iec 61850-6

    Section 3 1MRS756793 E Substation Configuration description Language (SCL) IET600 • A SCD file is to be opened or a SCD, ICD or CID file for the particular IED(s) is to be imported/merged. • For each IED, the data sets, the control blocks for reporting (this means unbufffered/buffered reporting and GOOSE) and the properties for each report control block are to be defined.
  • Page 30 Section 3 1MRS756793 E Substation Configuration description Language (SCL) Client B Client A System tool IED A IED B IED Z …. tool GUID-ACC3CE26-A7F7-4B88-A6DD-9B5104A5A10F V1 EN Figure 5: Relation between system and IED tools Regardless of engineering approach, the idea is that the IED tool provides the CID or ICD file for each IED.
  • Page 31: Section 4 Communication Profile

    Section 4 1MRS756793 E Communication profile Section 4 Communication profile The IEC 61850 standard is conceptually written to be independent of an existing communication media and message transmission concept. Out of this, a specific communication profile is decided and is been commonly used. The actual decision is •...
  • Page 32 Section 4 1MRS756793 E Communication profile Generic Generic Object Core Substation Sampled Oriented Time ACSI Status Values Substation Services Sync (Multicast) Event Event TimeSync GOOSE GSSE MMS Protocol Suite (SNTP) TCP/IP ISO CO GSSE UDP/IP T-Profile T-Profile T-Profile ISO/IEC 8802-2 LLC ISO/IEC 8802-3 Ethertype ISO/IEC 8802-3 GUID-8CA0E976-7104-4170-A92F-188D333E4C25 V1 EN...
  • Page 33: Section 5 Supported Services

    Section 5 1MRS756793 E Supported services Section 5 Supported services IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes how the services are applied in the communication. The conformance documents contain the description of the supported services in the IED. Services that are not mentioned in this chapter or in the conformance document are not supported.
  • Page 34 Section 5 1MRS756793 E Supported services Note that the parameters BufTm and IntPrd shall have the relation BufTm < IntPrd. For best efficiency, the BufTm should have IntPrd as common denominator, for example: n*BufTm = IntPrd, n is an arbitrary number. Generic substation event (GOOSE) The structured GOOSE is supported.
  • Page 35: Section 6 Data Sets And Control Blocks

    Section 6 1MRS756793 E Data sets and control blocks Section 6 Data sets and control blocks Data sets IEC 61850 has defined data sets and report control blocks for signal transmission in monitoring direction. Data sets are also used for GOOSE messages in horizontal direction.
  • Page 36: Report Control Block (Urcb/Brcb)

    Section 6 1MRS756793 E Data sets and control blocks • All data objects or their data attributes which are signals in monitoring direction can be selected for a data set. • Only those data attributes of a data object can/will be selected which have the same function constraint (FC).
  • Page 37 Section 6 1MRS756793 E Data sets and control blocks data set. This is done by the attribute Integrity period. This feature can be used as a background cycle to ensure that the process image in all partners is the same. The background cycle can repair a lost event in the chain from the NCC to an IED.
  • Page 38 Section 6 1MRS756793 E Data sets and control blocks start or restart a session. When the client is able to receive the actual values and when the logical device has scanned all process values at least once, an image of the actual process signal status can be transmitted to the client. Note that the possible trigger options for each attribute are included and defined in the data type template section in SCL.
  • Page 39: Goose Control Blocks (Gocb)

    Section 6 1MRS756793 E Data sets and control blocks GOOSE Control Blocks (GoCB) Data-set Data-set Data-set Subnetwork Comm. Comm. Server Server GoCB GoCB Input Input GoCB GoCB Input Input GoCB GoCB Input Input DataSet DataSet DataSet DataSet DataSet DataSet en06000109.vsd IEC06000109 V2 EN Figure 10: IEC 61850: Principle operation of GOOSE messages...
  • Page 40 Section 6 1MRS756793 E Data sets and control blocks The GOOSE service model of IEC 61850-7-2 provides the possibility for fast and reliable system-wide distribution of input and output data values. This implementation uses a specific scheme of retransmission to achieve the appropriate level of reliability.
  • Page 41 Section 6 1MRS756793 E Data sets and control blocks The GOOSE message concept is used for all application functions where two or more IEDs are involved. Typical example is the station-wide interlocking procedure or breaker failure protection. Figure Figure 10 shows the GOOSE concept for three IEDs which interchange GOOSE messages between each other.
  • Page 43: Section 7 Logical Node Data Model

    The IEC 61850 standard does not describe the functionality and way of operation. Each supplier has to describe this separately. ABB has described their function blocks that represent a logical node and all other function blocks in the technical manuals.
  • Page 44: Logical Nodes For Automatic Control

    Section 7 1MRS756793 E Logical node data model The mandatory data objects as defined in IEC 61850-7-4 as part of the Common Logical Node are Mode, Behavior, Health and NamePlate. Mode The operation modes ON (enabled) and BLOCKED are supported remotely by a command or locally from the LHMI of the IED.
  • Page 45 Section 7 1MRS756793 E Logical node data model Table 4: OLATCC Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 46 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description EndPosL a_dSPS Quality: Indication of extreme lower position caused blocking Timestamp: Indication of extreme lower position caused blocking CtlV b_dMV mag.f U_CTL Control voltage, Up, target voltage level U_CTL Quality: Control voltage, Up, target...
  • Page 47 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 LTCBlk c_dSPC stVal External signal for blocking of automatic operation status Quality: External signal for blocking of automatic operation...
  • Page 48 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description OpTmhNum v1_dINS OP_TM_NUM_H Timestamp: Number of controls for own tap changer during last hour TapOpErr v1_dSPS stVal ALARM Alarm status ALARM Quality: Alarm status ALARM Timestamp: Alarm status ErrParTra...
  • Page 49 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AngVAPhA v2_dMV ANGL_UA_IA Timestamp: Measured angle value between phase A voltage and current CtlVDif v2_dMV mag.f UD_CTL Voltage difference between measured and control Voltage UD_CTL Quality: Voltage difference between measured and control...
  • Page 50 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description NumParUnit v7_dINS PAR_UNIT_MCC Timestamp: Parallel units included in MCC calculation TapOpFllw1 v7_dINS stVal FLLW1_CTL Lower/Raise for follower 1 in the Master/Follower mode FLLW1_CTL Quality: Lower/Raise for follower 1 in the Master/Follower mode FLLW1_CTL...
  • Page 51: Logical Nodes For Control

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description EndPosR a_dSPS Timestamp: Indication of extreme raise position caused blocking TapChg b_dBSC valWTr.posVal Tap position status for IEC61850 mapping valWTr.transInd Tap changer operating status for IEC61850 mapping Quality: Tap position status for IEC61850 mapping...
  • Page 52 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Timestamp: a_dSPS stVal Local operation allowed Quality: Local operation allowed Timestamp: Local operation allowed LocSwPos v1_dINS stVal LR_POS Position of the Local/Remote switch LR_POS Quality: Position of the Local/...
  • Page 53: Interlocking Interface Scilo

    Section 7 1MRS756793 E Logical node data model 7.3.2 Interlocking interface SCILO LN type LN prefix LN class Function block name SCILO (revision 1) S CILO SCILO Table 8: SCILO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC...
  • Page 54: Switch Controller Cswi

    Section 7 1MRS756793 E Logical node data model 7.3.3 Switch controller CSWI LN type LN prefix LN class Function block name GNRLCSWI (revision 0) GNRL CSWI GNRLCSWI Table 9: GNRLCSWI Logical node data DO name DO type DA name Signal Mon/C Description a_dDPC...
  • Page 55 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dDPC stVal POSITION Position indication POSITION Quality: Position indication POSITION Timestamp: Position indication stSeld SELECTED The select conditions are fulfilled subEna Substitute enable subVal Substituted double position value ctlModel...
  • Page 56: Logical Nodes For Protection Functions

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description BlkCmd v1_dSPC Oper.Test Special block command value Oper.Check Special block command value stVal CMD_BLKD Commands are blocked CMD_BLKD Quality: Commands are blocked CMD_BLKD Timestamp: Commands are blocked Logical nodes for protection functions...
  • Page 57 Section 7 1MRS756793 E Logical node data model Table 11: DEFHPDEF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 58 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status parameter for 61850 OpAEF v2_dMV mag.f I_OPER Calculated operating current I_OPER Quality: Calculated operating current I_OPER Timestamp: Calculated operating current OpPolAng v2_dMV...
  • Page 59 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 Table 14: DEFLPDEF Logical node data (instance 1) DO name DO type DA name...
  • Page 60: Differential Protection Pdif

    Section 7 1MRS756793 E Logical node data model Table 15: DEFLPDEF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACD dirGeneral DIRECTION...
  • Page 61 Section 7 1MRS756793 E Logical node data model Table 16: HREFPDIF Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 62 Section 7 1MRS756793 E Logical node data model Table 17: MPDIF Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operate signal, combined (all phases, both stages) phsA OPR_A Operate signal, Phase A phsB OPR_B Operate signal, Phase B phsC...
  • Page 63 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RstA f_dWYE cVal.mag.f IB_B Bias current, phase B cVal.mag.f IB_C Bias current, phase C IB_C Quality: Bias current, phase C IB_B Quality: Bias current, phase B IB_A Quality: Bias current, phase A IB_A...
  • Page 64 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AngLinCA v2_dMV I_ANGL_C1_A1 Quality: Current phase angle Phase C – Phase A, line side I_ANGL_C1_A1 Timestamp: Current phase angle Phase C – Phase A, line side AngNeutAB v2_dMV mag.f...
  • Page 65 Section 7 1MRS756793 E Logical node data model Table 18: MHZPDIF Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operated phsA OPR_A Operated phase A phsB OPR_B Operated phase B phsC OPR_C Operated phase C OPERATE Quality: Operated OPERATE...
  • Page 66: Distance Protection Pdis

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DifAClc f_dWYE ID_B Timestamp: Analog output value phase B ID_C Timestamp: Analog output value phase C StrDur v2_dMV mag.f START_DUR Ratio of start time / operate time START_DUR Quality: Ratio of start time / operate time...
  • Page 67 Section 7 1MRS756793 E Logical node data model Table 19: DSTPDIS Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status parameter for 61850...
  • Page 68 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRea2 v2_dMV 1 FLTLOOP_XSND Z1 Timestamp: Record data of bank 1 for PE-loop reactance (2nd), Zone PPLoopRis v2_dMV mag.f 1 FLTLOOP_RPP Z1 Record data of bank 1 for PP-loop resistance, Zone Z1 1 FLTLOOP_RPP Z1 Quality: Record data of bank 1 for...
  • Page 69 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRis1 v2_dMV 1 FLTLOOP_RFST Z2 Timestamp: Record data of bank 1 for PE-loop resistance (1st), Zone PhLoopRea1 v2_dMV mag.f 1 FLTLOOP_XFST Z2 Record data of bank 1 for PE-loop reactance (1st), Zone Z2 1 FLTLOOP_XFST Z2 Quality: Record data of bank 1 for...
  • Page 70 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status parameter for 61850 DirRisZn v2_dMV mag.f 1 DIR_LOOP_R Z3 Record data of bank 1 for direction resistance, Zone Z3 1 DIR_LOOP_R Z3 Quality: Record data of bank 1 for direction resistance, Zone Z3...
  • Page 71 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PPLoopReac v2_dMV mag.f 1 FLTLOOP_XPP Z3 Record data of bank 1 for PP-loop reactance, Zone Z3 1 FLTLOOP_XPP Z3 Quality: Record data of bank 1 for PP-loop reactance, Zone Z3 1 FLTLOOP_XPP Z3 Timestamp: Record data of bank 1...
  • Page 72 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRis2 v2_dMV mag.f 1 FLTLOOP_RSND AR1 Record data of bank 1 for PE-loop resistance (2nd), Zone AR1 1 FLTLOOP_RSND AR1 Quality: Record data of bank 1 for PE-loop resistance (2nd), Zone 1 FLTLOOP_RSND AR1 Timestamp: Record data of bank 1...
  • Page 73 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DirReactZn v2_dMV mag.f 1 DIR_LOOP_X AR2 Record data of bank 1 for direction reactance, Zone AR2 1 DIR_LOOP_X AR2 Quality: Record data of bank 1 for direction reactance, Zone AR2 1 DIR_LOOP_X AR2 Timestamp: Record data of bank 1...
  • Page 74 Section 7 1MRS756793 E Logical node data model Table 24: DSTPDIS Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 75 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status parameter for 61850 DirRisZn v2_dMV mag.f 3 DIR_LOOP_R Z1 Record data of bank 3 for direction resistance, Zone Z1 3 DIR_LOOP_R Z1 Quality: Record data of bank 3 for direction resistance, Zone Z1...
  • Page 76 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PPLoopReac v2_dMV mag.f 3 FLTLOOP_XPP Z1 Record data of bank 3 for PP-loop reactance, Zone Z1 3 FLTLOOP_XPP Z1 Quality: Record data of bank 3 for PP-loop reactance, Zone Z1 3 FLTLOOP_XPP Z1 Timestamp: Record data of bank 3...
  • Page 77 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRis2 v2_dMV mag.f 2 FLTLOOP_RSND Z2 Record data of bank 2 for PE-loop resistance (2nd), Zone Z2 2 FLTLOOP_RSND Z2 Quality: Record data of bank 2 for PE-loop resistance (2nd), Zone Z2 2 FLTLOOP_RSND Z2 Timestamp: Record data of bank 2...
  • Page 78 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DirReactZn v2_dMV mag.f 3 DIR_LOOP_X Z2 Record data of bank 3 for direction reactance, Zone Z2 3 DIR_LOOP_X Z2 Quality: Record data of bank 3 for direction reactance, Zone Z2 3 DIR_LOOP_X Z2 Timestamp: Record data of bank 3...
  • Page 79 Section 7 1MRS756793 E Logical node data model Table 28: DSTPDIS Logical node data (instance 10) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status parameter for 61850...
  • Page 80 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRea2 v2_dMV 2 FLTLOOP_XSND Z3 Timestamp: Record data of bank 2 for PE-loop reactance (2nd), Zone PPLoopRis v2_dMV mag.f 2 FLTLOOP_RPP Z3 Record data of bank 2 for PP-loop resistance, Zone Z3 2 FLTLOOP_RPP Z3 Quality: Record data of bank 2 for...
  • Page 81 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRis1 v2_dMV 3 FLTLOOP_RFST Z3 Timestamp: Record data of bank 3 for PE-loop resistance (1st), Zone PhLoopRea1 v2_dMV mag.f 3 FLTLOOP_XFST Z3 Record data of bank 3 for PE-loop reactance (1st), Zone Z3 3 FLTLOOP_XFST Z3 Quality: Record data of bank 3 for...
  • Page 82 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status parameter for 61850 DirRisZn v2_dMV mag.f 2 DIR_LOOP_R AR1 Record data of bank 2 for direction resistance, Zone AR1 2 DIR_LOOP_R AR1 Quality: Record data of bank 2 for direction resistance, Zone AR1...
  • Page 83 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PPLoopRis v2_dMV 2 FLTLOOP_RPP AR1 Timestamp: Record data of bank 2 for PP-loop resistance, Zone AR1 PPLoopReac v2_dMV mag.f 2 FLTLOOP_XPP AR1 Record data of bank 2 for PP-loop reactance, Zone AR1 2 FLTLOOP_XPP AR1 Quality: Record data of bank 2 for...
  • Page 84 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRea1 v2_dMV 3 FLTLOOP_XFST AR1 Timestamp: Record data of bank 3 for PE-loop reactance (1st), Zone PhLoopRis2 v2_dMV mag.f 3 FLTLOOP_RSND AR1 Record data of bank 3 for PE-loop resistance (2nd), Zone AR1 3 FLTLOOP_RSND AR1 Quality: Record data of bank 3 for...
  • Page 85 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DirRisZn v2_dMV 2 DIR_LOOP_R AR2 Quality: Record data of bank 2 for direction resistance, Zone AR2 2 DIR_LOOP_R AR2 Timestamp: Record data of bank 2 for direction resistance, Zone AR2 DirReactZn v2_dMV...
  • Page 86 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PPLoopReac v2_dMV mag.f 2 FLTLOOP_XPP AR2 Record data of bank 2 for PP-loop reactance, Zone AR2 2 FLTLOOP_XPP AR2 Quality: Record data of bank 2 for PP-loop reactance, Zone AR2 2 FLTLOOP_XPP AR2 Timestamp: Record data of bank 2...
  • Page 87 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhLoopRis2 v2_dMV mag.f 3 FLTLOOP_RSND AR2 Record data of bank 3 for PE-loop resistance (2nd), Zone AR2 3 FLTLOOP_RSND AR2 Quality: Record data of bank 3 for PE-loop resistance (2nd), Zone 3 FLTLOOP_RSND AR2 Timestamp: Record data of bank 3...
  • Page 88 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DirReactZn v2_dMV mag.f 2 DIR_LOOP_X Z1 Record data of bank 2 for direction reactance, Zone Z1 2 DIR_LOOP_X Z1 Quality: Record data of bank 2 for direction reactance, Zone Z1 2 DIR_LOOP_X Z1 Timestamp: Record data of bank 2...
  • Page 89 Section 7 1MRS756793 E Logical node data model Table 35: DSTPDIS Logical node data (instance 5) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE_ZAR2...
  • Page 90 Section 7 1MRS756793 E Logical node data model Table 36: DSTPDIS Logical node data (instance 4) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE_ZAR1...
  • Page 91 Section 7 1MRS756793 E Logical node data model Table 37: DSTPDIS Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE_Z1...
  • Page 92 Section 7 1MRS756793 E Logical node data model Table 38: DSTPDIS Logical node data (instance 3) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE_Z3...
  • Page 93 Section 7 1MRS756793 E Logical node data model Table 39: DSTPDIS Logical node data (instance 2) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE_Z2...
  • Page 94 Section 7 1MRS756793 E Logical node data model Table 40: DSTPDIS Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACD dirGeneral DIRECTION...
  • Page 95 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description EFDet v2_dSPS 1 EARTH_FLT GFC Timestamp: Record data of bank 1 for earth-fault, GFC XCDet v2_dSPS stVal 1 XC_FLT GFC Record data of bank 1 for cross country fault, GFC 1 XC_FLT GFC Quality: Record data of bank 1 for...
  • Page 96 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description EFDir v2_dACD dirGeneral 2 DIR_E_FLT GFC Record data of bank 2 for EF- direction, GFC 2 DIR_E_FLT GFC Quality: Record data of bank 2 for EF-direction, GFC 2 DIR_E_FLT GFC Timestamp: Record data of bank 2...
  • Page 97 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD 3 DIRECTION Quality: Record data of bank 3 for direction 3 DIRECTION Timestamp: Record data of bank 3 for direction c_dINC stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850...
  • Page 98 Section 7 1MRS756793 E Logical node data model Table 44: DSTPDIS Logical node data (instance 6) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE_GFC...
  • Page 99 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RelPhsBC v1_dSPS stVal Event release phase B to phase C Quality: Event release phase B to phase C Timestamp: Event release phase B to phase C RelPhsCA v1_dSPS stVal...
  • Page 100 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD DIR_E_FLT Quality: Earth-fault direction (low imp. earthed), GFC DIR_E_FLT Timestamp: Earth-fault direction (low imp. earthed), GFC c_dINC stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status...
  • Page 101 Section 7 1MRS756793 E Logical node data model Table 47: UZPDIS Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status value parameter for...
  • Page 102 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status value parameter for 61850 d_dACD general START Started START Quality: Started START Timestamp: Started StrDur v2_dMV mag.f START_DUR Ratio of start time / operate time (in START_DUR Quality: Ratio of start time / operate time (in %)
  • Page 103 Section 7 1MRS756793 E Logical node data model Table 50: UEXPDIS Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status value parameter for...
  • Page 104 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description v1_dDEL cVal.mag.f Z_AMPL_AB Phase-to-phase A-B impedance amplitude cVal.ang.f Z_ANGLE_CA Phase-to-phase C-A impedance phase angle Z_AMPL_AB Quality: Phase-to-phase A-B impedance amplitude Z_AMPL_CA Quality: Phase-to-phase C-A impedance amplitude Z_AMPL_BC Quality: Phase-to-phase B-C...
  • Page 105: Directional Overcurrent Pdoc

    Section 7 1MRS756793 E Logical node data model 7.4.4 Directional overcurrent PDOC LN type LN prefix LN class Function block name DPHPTOC instance 1 (revision 0) DPH PTOC DPHHPDOC DPHRDIR instance 1 (revision 0) RDIR DPHHPDOC PHBLLN0 instance 1 (revision 0) LLN0 DPHHPDOC Table 52:...
  • Page 106 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description StrDur v2_dMV mag.f START_DUR Ratio of start time / operate time START_DUR Quality: Ratio of start time / operate time START_DUR Timestamp: Ratio of start time / operate time Table 53: DPHHPDOC Logical node data (instance 1)
  • Page 107 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Timestamp: Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 LN type LN prefix LN class Function block name DPHPTOC instance 1 (revision 0) DPH...
  • Page 108 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status parameter for 61850 IvdCrv v1_dSPS stVal INVAL_CRV Invalid curve parameters INVAL_CRV Quality: Invalid curve parameters INVAL_CRV Timestamp: Invalid curve parameters StrDur v2_dMV...
  • Page 109: Overcurrent Protection Pvoc

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 a_dINS...
  • Page 110: Rate Of Change Of Frequency Pfrc

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dACD general START Started phsA ST_A Start signal for phase A phsB ST_B Start signal for phase B phsC...
  • Page 111: Frequency Protection Pfrq

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 a_dINS stVal...
  • Page 112 Section 7 1MRS756793 E Logical node data model Table 60: LSHDPFRQ Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 113 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status value parameter for 61850 d_dACD general ST_FRG Pick-Up signal for high df/dt detection ST_FRG Quality: Pick-Up signal for high df/ dt detection ST_FRG Timestamp: Pick-Up signal for...
  • Page 114 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description ManRest v1_dSPC Oper.Check Command parameter for IEC61850 RestLodOp v2_dACT general RESTORE Restore signal for load restoring purposes RESTORE Quality: Restore signal for load restoring purposes RESTORE Timestamp: Restore signal for...
  • Page 115: Harmonic Distortion Phar

    Section 7 1MRS756793 E Logical node data model 7.4.8 Harmonic distortion PHAR LN type LN prefix LN class Function block name INRPHAR (revision 0) INR PHAR INRPHAR Table 64: INRPHAR Logical node data DO name DO type DA name Signal Mon/C Description a_dINC...
  • Page 116: Motor Supervision Pmsu

    Section 7 1MRS756793 E Logical node data model Table 65: DSTPLAL Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter...
  • Page 117 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850 Timestamp: Mode status value...
  • Page 118 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Timestamp: Mode status value parameter for 61850 StUpCnt v1_dINS stVal START_CNT Number of motor start-ups occurred START_CNT Quality: Number of motor start-ups occurred START_CNT Timestamp: Number of motor...
  • Page 119: Restricted Earth Fault Pndf

    Section 7 1MRS756793 E Logical node data model Table 68: STTPMSU Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPR_STALL...
  • Page 120 Section 7 1MRS756793 E Logical node data model Table 69: LREFPNDF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status parameter for 61850...
  • Page 121 Section 7 1MRS756793 E Logical node data model Table 71: LREFPNDF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 122: Protection Scheme Psch

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description StrDur v2_dMV mag.f START_DUR Start duration in percentage of the total operating time START_DUR Quality: Start duration in percentage of the total operating time START_DUR Timestamp: Start duration in...
  • Page 123 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description ProRx a_dSPS stVal POR Carrier signal received from remote end Quality: POR Carrier signal received from remote end Timestamp: POR Carrier signal received from remote end ProTx a_dSPS stVal...
  • Page 124 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter...
  • Page 125 Section 7 1MRS756793 E Logical node data model Table 74: RCRWPSCH Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter...
  • Page 126 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RvABlk b_dACT OPR_IRV Timestamp: Operation of current reversal logic WeiOp b_dACT general OPR_WEI Operation of WEI logic OPR_WEI Quality: Operation of WEI logic OPR_WEI Timestamp: Operation of WEI logic...
  • Page 127: Transient Earth Fault Ptef

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description ProTx a_dSPS Quality: Teleprotection signal transmitted for a forward fault Timestamp: Teleprotection signal transmitted for a forward fault b_dACD general Carrier Send by Communication Scheme Logic dirGeneral Directional attribute of Carrier...
  • Page 128: Transformer Differential Ptdf

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Timestamp: Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 129 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dACD general 2nd harmonic restraint blocking for PHAR LN, combined phsA 2nd harmonic restraint blocking for PHAR LN, phase A phsB 2nd harmonic restraint blocking for PHAR LN, phase B phsC 2nd harmonic restraint blocking for...
  • Page 130 Section 7 1MRS756793 E Logical node data model Table 79: TR2PTDF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operate signal, combined (all phases, both stages) phsA OPR_A Operate signal phase A phsB OPR_B Operate signal phase B...
  • Page 131 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description Blk5HSt v1_dACT general BLKD5H Status from 5th harmonic restraint blocking, combined phsA BLKD5H_A Status from 5th harmonic restraint blocking, phase A phsB BLKD5H_B Status from 5th harmonic restraint blocking, phase B phsC...
  • Page 132 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AngScyBC v2_dMV mag.f I_ANGL_B2_C2 Current phase angle phase B – phase C, winding 2 I_ANGL_B2_C2 Quality: Current phase angle phase B – phase C, winding 2 I_ANGL_B2_C2 Timestamp: Current phase angle phase B –...
  • Page 133: Time Overcurrent Ptoc

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dACD Timestamp: 5th harmonic restraint blocking for PHAR LN, combined a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal...
  • Page 134 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT general OPERATE Operated OPERATE Quality: Operated OPERATE Timestamp: Operated StrDur v2_dMV mag.f START_DUR Ratio of start time / operate time START_DUR Quality: Ratio of start time / operate time START_DUR Timestamp: Ratio of start time /...
  • Page 135 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description StrDur v2_dMV mag.f START_DUR Start duration in percentage of the total operating time START_DUR Quality: Start duration in percentage of the total operating time START_DUR Timestamp: Start duration in...
  • Page 136 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description StrDur v2_dMV mag.f START_DUR Ratio of start time / operate time START_DUR Quality: Ratio of start time / operate time START_DUR Timestamp: Ratio of start time / operate time LN type LN prefix LN class Function block name...
  • Page 137 Section 7 1MRS756793 E Logical node data model LN type LN prefix LN class Function block name EFLPTOC (revision 0) EFL PTOC EFLPTOC Table 85: EFLPTOC Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850...
  • Page 138 Section 7 1MRS756793 E Logical node data model Table 86: NSPTOC Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 139 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 a_dINS...
  • Page 140 Section 7 1MRS756793 E Logical node data model Table 88: PHHPTOC Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operated phsA OPR_A Operated phase A phsB OPR_B Operated phase B phsC OPR_C Operated phase C OPERATE Quality: Operated OPERATE...
  • Page 141 Section 7 1MRS756793 E Logical node data model Table 89: PHIPTOC Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operated phsA OPR_A Operated phase A phsB OPR_B Operated phase B phsC OPR_C Operated phase C OPERATE Quality: Operated OPERATE...
  • Page 142 Section 7 1MRS756793 E Logical node data model Table 90: PHLPTOC Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operated phsA OPR_A Operated phase A phsB OPR_B Operated phase B phsC OPR_C Operated phase C OPERATE Quality: Operated OPERATE...
  • Page 143 Section 7 1MRS756793 E Logical node data model MRE2PTOC instance 1 (revision 0) MRE2 PTOC MREFPTOC RESBLLN0 instance 1 (revision 0) LLN0 MREFPTOC Table 91: MREFPTOC Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850...
  • Page 144 Section 7 1MRS756793 E Logical node data model Table 93: MREFPTOC Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 145 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 Table 95: HAEFPTOC Logical node data (instance 1) DO name DO type DA name...
  • Page 146 Section 7 1MRS756793 E Logical node data model Table 96: HAEFPTOC Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 147: Overfrequency Ptof

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 a_dINS stVal...
  • Page 148 Section 7 1MRS756793 E Logical node data model Table 98: DAPTOF Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter...
  • Page 149: Overvoltage Ptov

    Section 7 1MRS756793 E Logical node data model 7.4.17 Overvoltage PTOV LN type LN prefix LN class Function block name NSPTOV (revision 0) NS PTOV NSPTOV Table 99: NSPTOV Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal...
  • Page 150 Section 7 1MRS756793 E Logical node data model LN type LN prefix LN class Function block name PHPTOV (revision 0) PH PTOV PHPTOV Table 100: PHPTOV Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operate signal, combined phsA...
  • Page 151 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VMax v2_dMV mag.f U_MAX Maximum of the phase or phase- to-phase voltages U_MAX Quality: Maximum of the phase or phase-to-phase voltages U_MAX Timestamp: Maximum of the phase or phase-to-phase voltages VMaxRat v2_dMV...
  • Page 152 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description d_dACD general START Start signal for Positive Sequence Overvoltage logic START Quality: Start signal for Positive Sequence Overvoltage logic START Timestamp: Start signal for Positive Sequence Overvoltage logic StrDur...
  • Page 153: Protection Trip Conditioning Ptrc

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT OPERATE Timestamp: Operate signal for residual overvoltage logic d_dACD general START Start signal for residual overvoltage logic START Quality: Start signal for residual overvoltage logic START Timestamp: Start signal for...
  • Page 154: Thermal Overload Pttr

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT TRIP Timestamp: General trip output signal LORs v1_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for...
  • Page 155 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Timestamp: Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 AlmThm a_dSPS stVal...
  • Page 156 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SenFlt v1_dSPS stVal Error signal from the temperature sensor Quality: Error signal from the temperature sensor Timestamp: Error signal from the temperature sensor ThmDev v2_dMV mag.f...
  • Page 157 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for...
  • Page 158 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TmsOp v1_dINS T_OPERATE Quality: Estimated time to operate T_OPERATE Timestamp: Estimated time to operate TmsRecEna v1_dINS stVal T_ENA_CLOSE Estimated time to deactivate BLK_CLOSE in seconds T_ENA_CLOSE Quality: Estimated time to deactivate BLK_CLOSE in...
  • Page 159: St Toperate

    Section 7 1MRS756793 E Logical node data model Table 106: T1PTTR Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter...
  • Page 160: Time Undercurrent Ptuc

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TmmRecEna v1_dINS T_ENA_CLOSE Quality: Estimated time to reset of block reclose T_ENA_CLOSE Timestamp: Estimated time to reset of block reclose RsTmp v1_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat...
  • Page 161: Undervoltage Ptuv

    Section 7 1MRS756793 E Logical node data model Table 107: LOFLPTUC Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 162 Section 7 1MRS756793 E Logical node data model Table 108: PHPTUV Logical node data DO name DO type DA name Signal Mon/C Description a_dACT general OPERATE Operate signal, combined phsA OPR_A Operate signal, phase 1 phsB OPR_B Operate signal, phase 2 phsC OPR_C Operate signal, phase 3...
  • Page 163 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VMinRat v2_dMV mag.f U_RATIO Minimum voltage ratio to the Start value U_RATIO Quality: Minimum voltage ratio to the Start value U_RATIO Timestamp: Minimum voltage ratio to the Start value LN type LN prefix LN class Function block name...
  • Page 164 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description d_dACD START Timestamp: Start signal for Positive Sequence Undervoltage logic StrDur v2_dMV mag.f START_DUR Start duration in percentage of the total operating time START_DUR Quality: Start duration in percentage of the total operating...
  • Page 165 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description d_dACD general START Started START Quality: Started START Timestamp: Started LN type LN prefix LN class Function block name DQLLN0 instance 1 (revision 0) LLN0 DQPTUV DQMMXU instance 1 (revision 0) DQ...
  • Page 166 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TotVAr b_dMV mag.f Calculated positive sequence reactive power Quality: Calculated positive sequence reactive power Timestamp: Calculated positive sequence reactive power c_dINC stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850...
  • Page 167: Vector Shift Ppam

    Section 7 1MRS756793 E Logical node data model Table 114: DQPTUV Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 168 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850...
  • Page 169: Underfrequency Ptuf

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VShtPsSeq v2_dMV mag.f VEC_SHT_U1 Vector shift for positive sequence voltage VEC_SHT_U1 Quality: Vector shift for positive sequence voltage VEC_SHT_U1 Timestamp: Vector shift for positive sequence voltage 7.4.23 Underfrequency PTUF...
  • Page 170: Admittance-Based Earth-Fault Protection Padm

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT OPERATE Timestamp: Operate signal for underfrequency protection d_dACD general START Start signal for underfrequency protection START Quality: Start signal for underfrequency protection START Timestamp: Start signal for underfrequency protection...
  • Page 171 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD 1 FAULT_DIR Timestamp: Record data of bank 1 for detected fault direction c_dINC stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850...
  • Page 172 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhVPreFlt v5_dWYE 1 U_AMPL_RES Pre Flt Timestamp: Record data of bank 1 for magnitude of pre-fault residual voltage AFlt v5_dWYE cVal.mag.f 1 I_AMPL_RES fault Record data of bank 1 for magnitude of fault-state residual current...
  • Page 173 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description Cond v2_dMV 2 COND_RES (Go) Quality: Record data of bank 2 for real part of neutral admittance 2 COND_RES (Go) Timestamp: Record data of bank 2 for real part of neutral admittance v2_dMV mag.f...
  • Page 174 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AFlt v5_dWYE 2 I_AMPL_RES fault Timestamp: Record data of bank 2 for magnitude of fault-state residual current PhVFlt v5_dWYE cVal.mag.f 2 U_AMPL_RES fault Record data of bank 2 for magnitude of fault-state residual voltage...
  • Page 175 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description StrDur v2_dMV mag.f 3 START_DUR Record data of bank 3 for ratio of started time / operate time 3 START_DUR Quality: Record data of bank 3 for ratio of started time / operate time 3 START_DUR Timestamp: Record data of bank 3...
  • Page 176 Section 7 1MRS756793 E Logical node data model Table 120: EFPADM Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 177 Section 7 1MRS756793 E Logical node data model Table 121: EFPADM Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 178: Multi-Frequency Neutral Admittance Earth-Fault Protection Psde

    Section 7 1MRS756793 E Logical node data model 7.4.25 Multi-frequency neutral admittance earth-fault protection PSDE LN type LN prefix LN class Function block name GNRLLLN0 instance 1 (revision 0) LLN0 MFADPSDE MFADPSDE instance 1 (revision 0) MFAD PSDE MFADPSDE MFADRDIR instance 1 (revision 0) MFAD RDIR MFADPSDE...
  • Page 179 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 d_dACD general START Start signal dirGeneral FAULT_DIR Detected fault direction START Quality: Start signal START...
  • Page 180: Directional Power Protection Pdpr

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 OpPolAng v2_dMV mag.f ANGLE Angle between polarizing and operating quantity ANGLE Quality: Angle between polarizing...
  • Page 181 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TotPFAng v2_dMV mag.f PF_ANGL Angle between apparent power and active power PF_ANGL Quality: Angle between apparent power and active power PF_ANGL Timestamp: Angle between apparent power and active power Table 126: DOPPDPR Logical node data (instance 1)
  • Page 182 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 a_dINS...
  • Page 183 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TotPFAng v2_dMV mag.f PF_ANGL Angle between apparent power and active power PF_ANGL Quality: Angle between apparent power and active power PF_ANGL Timestamp: Angle between apparent power and active power Table 129: DUPPDPR Logical node data (instance 1)
  • Page 184: Volts Per Hz Pvph

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 a_dINS...
  • Page 185: Directional Earth Fault Wattmetric Pwde

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description StrInh a_dSPS BLK_RESTART Quality: Signal for blocking reconnection of an overheated machine BLK_RESTART Timestamp: Signal for blocking reconnection of an overheated machine b_dACD general START Started...
  • Page 186 Section 7 1MRS756793 E Logical node data model Table 132: WPWDE Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 187 Section 7 1MRS756793 E Logical node data model Table 134: WPWDE Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general OPERATE...
  • Page 188: Stator Earth-Fault Protection Psef

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description OpPolAng v2_dMV ANGLE Quality: Angle between polarizing and operating quantity ANGLE Timestamp: Angle between polarizing and operating quantity OpChrAng v2_dMV mag.f ANGLE_RCA Angle between operating angle and characteristic angle ANGLE_RCA Quality: Angle between operating...
  • Page 189 Section 7 1MRS756793 E Logical node data model Table 137: H3EFPSEF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general Third harmonic differential over...
  • Page 190 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description Term3HV v2_dMV U_3H_T_AMPL Timestamp: Terminal side third harmonic voltage amplitude N3HV v2_dMV mag.f U_3H_N_AMPL Neutral side third harmonic voltage amplitude U_3H_N_AMPL Quality: Neutral side third harmonic voltage amplitude U_3H_N_AMPL Timestamp: Neutral side third...
  • Page 191: Multipurpose Analog Protection Gapc

    Section 7 1MRS756793 E Logical node data model Table 139: H3EFPSEF Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general Third harmonic neutral under...
  • Page 192: System Logical Nodes

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850...
  • Page 193: Logical Nodes For Protection Related Functions

    Section 7 1MRS756793 E Logical node data model Logical nodes for protection related functions 7.6.1 Breaker failure RBRF LN type LN prefix LN class Function block name CCBRBRF (revision 0) CCB RBRF CCBRBRF Table 142: CCBRBRF Logical node data DO name DO type DA name Signal...
  • Page 194: Disturbance Recorder Rdre

    Section 7 1MRS756793 E Logical node data model Table 143: CCRDIF Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 195 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status...
  • Page 196: Fault Locator Rflo

    Section 7 1MRS756793 E Logical node data model 7.6.4 Fault locator RFLO LN type LN prefix LN class Function block name F1MSTA instance 1 (revision 0) MSTA SCEFRFLO FMSTA instance 1 (revision 0) MSTA SCEFRFLO FMSTA instance 2 (revision 0) MSTA SCEFRFLO RSLLN0 instance 1 (revision 0)
  • Page 197 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description FltR v2_dMV mag.f 1 RF Record data of bank 1 for fault resistance 1 RF Quality: Record data of bank 1 for fault resistance 1 RF Timestamp: Record data of bank 1 for fault resistance...
  • Page 198 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VPreFltPhB v2_dMV mag.f 1 PhV Pre value PhB Record data of bank 1 for phase B pre-fault voltage amplitude 1 PhV Pre value PhB Quality: Record data of bank 1 for phase B pre-fault voltage amplitude...
  • Page 199 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VFltPhB v2_dMV 1 PhV Flt value PhB Quality: Record data of bank 1 for phase B voltage amplitude during fault 1 PhV Flt value PhB Timestamp: Record data of bank 1 for phase B voltage amplitude during fault...
  • Page 200 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dSPS 2 ALARM Quality: Record data of bank 2 for alarm signal 2 ALARM Timestamp: Record data of bank 2 for alarm signal FltDiskm b_dMV mag.f...
  • Page 201 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PhGndCapac v2_dMV 2 XC0F_CALC Quality: Record data bank2 feeder phase-to-earth capacitive reactance 2 XC0F_CALC Timestamp: Record data bank2 feeder phase-to-earth capacitive reactance EqDisLod v2_dMV mag.f 2 S_CALC...
  • Page 202 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description APreFltPhA v2_dMV 2 A Pre value PhA Timestamp: Record data of bank 2 for phase A pre-fault current amplitude APreFltPhB v2_dMV mag.f 2 A Pre value PhB Record data of bank 2 for phase B pre-fault current amplitude 2 A Pre value PhB...
  • Page 203 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AFltPhC v2_dMV mag.f 2 A Flt value PhC Record data of bank 2 for phase C current amplitude during fault 2 A Flt value PhC Quality: Record data of bank 2 for phase C current amplitude during fault...
  • Page 204 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description FltDisVald v1_dINS stVal 3 EF_VALIDITY Record data of bank 3 for validity of earth fault location 3 EF_VALIDITY Quality: Record data of bank 3 for validity of earth fault location 3 EF_VALIDITY Timestamp: Record data of bank 3...
  • Page 205 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VPreFltPhA v2_dMV 3 PhV Pre value PhA Quality: Record data of bank 3 for phase A pre-fault voltage amplitude 3 PhV Pre value PhA Timestamp: Record data of bank 3 for phase A pre-fault voltage amplitude...
  • Page 206 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VFltPhB v2_dMV 3 PhV Flt value PhB Timestamp: Record data of bank 3 for phase B voltage amplitude during fault VFltPhC v2_dMV mag.f 3 PhV Flt value PhC Record data of bank 3 for phase C voltage amplitude during fault...
  • Page 207 Section 7 1MRS756793 E Logical node data model Table 148: SCEFRFLO Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 208 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description FltZ c_dCMV Timestamp: Fault resistance in primary ohms c_dINC stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 FltDiskm c_dMV...
  • Page 209: Fuse Failure Supervision Rfuf

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description FltLoopX v2_dMV XFLOOP Timestamp: Fault loop reactance in primary ohms PhGndCapac v2_dMV mag.f XC0F_CALC Estimated phase-to-earth capacitive reactance of the feeder XC0F_CALC Quality: Estimated phase-to-earth capacitive reactance of the feeder XC0F_CALC Timestamp: Estimated phase-to-...
  • Page 210: Autoreclosing Rrec

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Timestamp: Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 d_dACD general FUSEF_U...
  • Page 211 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Timestamp: Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general CLOSE_CB...
  • Page 212 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description OpCnt4 j_dINS stVal CNT_SHOT4 Resetable operation counter, shot CNT_SHOT4 Quality: Resetable operation counter, shot 4 CNT_SHOT4 Timestamp: Resetable operation counter, shot 4 OpCnt5 j_dINS stVal CNT_SHOT5...
  • Page 213 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RsCnt v1_dSPC Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 DsaCnt v1_dSPC Oper.ctlVal Command parameter for...
  • Page 214 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RdyRec v1_dSPS READY Quality: Indicates that the AR is ready for a new sequence READY Timestamp: Indicates that the AR is ready for a new sequence ActRec v1_dSPS stVal...
  • Page 215: Switch Onto Fault Logic Rsof

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description PrgDsr v1_dSPS DISCR_INPRO Timestamp: Signal indicating that discrimination time is inprogress PrgCutOut v1_dSPS stVal CUTOUT_INPRO Signal indicating that cut-out time is in progress CUTOUT_INPRO Quality: Signal indicating that cut- out time is in progress...
  • Page 216: Synchronising Rsyn

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850...
  • Page 217 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dSPS stVal Automatic release Quality: Automatic release Timestamp: Automatic release VInd a_dSPS stVal U_DIFF_SYNC Voltage difference out of limit U_DIFF_SYNC Quality: Voltage difference out of limit U_DIFF_SYNC Timestamp: Voltage difference out...
  • Page 218 Section 7 1MRS756793 E Logical node data model Table 154: SYNCRSYN Logical node data (instance 2) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 a_dSPS stVal Manual release...
  • Page 219 Section 7 1MRS756793 E Logical node data model Table 155: SYNCRSYN Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 220 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TestEnOK v1_dSPS ENERG_TST Quality: Energizing check OK test output ENERG_TST Timestamp: Energizing check OK test output VInBnd v1_dSPS stVal U_OK Voltage amplitudes above set limits U_OK Quality: Voltage amplitudes above...
  • Page 221: Logical Nodes For Generic References

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TestSynOK v1_dSPS SYN_TST Quality: Synchronizing OK test output SYN_TST Timestamp: Synchronizing OK test output HzRCInd v1_dSPS stVal FR_DER_SYN Frequency derivative out of limit for synchronizing FR_DER_SYN Quality: Frequency derivative out...
  • Page 222: Generic Process I/O Ggio

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Timestamp: Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 b_dACT general ST_EMERG_ENA...
  • Page 223 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DPCSO b_dDPC stVal POSITION Double point indication POSITION Quality: Double point indication POSITION Timestamp: Double point indication LN type LN prefix LN class Function block name CNTGGIO (revision 1) CNT GGIO CNTGGIO...
  • Page 224 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description Cnt5 v1_dBCR actVal VALUE5 Output of counter 5 VALUE5 Quality: Output of counter 5 VALUE5 Timestamp: Output of counter 5 Cnt6 v1_dBCR actVal VALUE6 Output of counter 6 VALUE6...
  • Page 225 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Timestamp: Behaviour parameter for 61850 c_dSPS stVal Output status Quality: Output status Timestamp: Output status LN type LN prefix LN class Function block name MVGGIO (revision 1) MV GGIO MVGGIO...
  • Page 226 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AnIn a_dMV VALUE Timestamp: Magnitude of deadband value subEna Enable substitution MV db Cycl: Report interval (s), Db: In % of range, Int Db: In %s zeroDb MV zeroDb Zero point clamping in 0,001% of...
  • Page 227 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description IcpCyc v1_dSPS stVal RESTART The reported value does not comprise a complete integration cycle RESTART Quality: The reported value does not comprise a complete integration cycle RESTART Timestamp: The reported value...
  • Page 228 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DPCSO d_dDPC Oper.origin.orCat Command parameter for IEC61850 SBOw.ctlVal Command parameter for IEC61850 SBOw.origin.orCat Command parameter for IEC61850 SBOw.origin.orIdent Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Cancel.origin.orIdent...
  • Page 229 Section 7 1MRS756793 E Logical node data model Table 164: SLGGIO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter...
  • Page 230 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SPCCO v2_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test...
  • Page 231 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SPCSO1 v2_dSPC Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check...
  • Page 232 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SPCSO3 v2_dSPC OUT3 Quality: Output3 OUT3 Timestamp: Output3 SPCSO4 v2_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for...
  • Page 233 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SPCSO6 v2_dSPC Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 stVal OUT6 Output6 OUT6 Quality: Output6 OUT6 Timestamp: Output6 SPCSO7 v2_dSPC Oper.ctlVal Command parameter for IEC61850...
  • Page 234: Logical Nodes For Metering And Measurement

    Section 7 1MRS756793 E Logical node data model Logical nodes for metering and measurement 7.8.1 Metering MMTR LN type LN prefix LN class Function block name EPDLLN0 instance 1 (revision 0) LLN0 EPDMMTR EPDMMTR instance 1 (revision 0) MMTR EPDMMTR EPDMMXU instance 1 (revision 0) EPD MMXU EPDMMTR...
  • Page 235 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DmdWh a_dBCR EAFACM_BCR Quality: Accumulated forward active energy value (BCR) EAFACM_BCR Timestamp: Accumulated forward active energy value (BCR) pulsQty Forward Wh Acc Pls Pulse quantity for active forward accumulated energy value SupVArh...
  • Page 236 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DmdVArhCnt v1_dINS ERFCNT Quality: Counter for accumulated forward reactive energy exceed limit ERFCNT Timestamp: Counter for accumulated forward reactive energy exceed limit SupVArhCnt v1_dINS stVal ERRCNT...
  • Page 237 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VArhFwdAlm v1_dSPS ERFAL Quality: Alarm for reactive forward energy exceed limit in set interv ERFAL Timestamp: Alarm for reactive forward energy exceed limit in set interv VArhRvAlm v1_dSPS...
  • Page 238 Section 7 1MRS756793 E Logical node data model Table 168: EPDMMTR Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status parameter for 61850...
  • Page 239: Measurement Mmxu

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VArRvDmd v2_dMV mag.f PRRDMD Last reverse reactive power demand value for set interval PRRDMD Quality: Last reverse reactive power demand value for set interval PRRDMD Timestamp: Last reverse reactive...
  • Page 240 Section 7 1MRS756793 E Logical node data model Table 169: CMMXU Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 241 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dWYE cVal.mag.f I_DB_C Phase C amplitude, magnitude of reported value subCVal.mag.f Substituted value subCVal.mag.f Substituted value range I_RANGE_C Phase C amplitude range range I_RANGE_A Phase A amplitude range range...
  • Page 242 Section 7 1MRS756793 E Logical node data model Table 170: PWRMMXU Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter...
  • Page 243 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TotVA a_dMV rangeC.max.f Tot apparent Pwr Max Maximum value subMag.f Substituted value range S_RANGE Apparent Power range S_DB Quality: Apparent Power magnitude of deadband value S_DB Timestamp: Apparent Power magnitude of deadband value...
  • Page 244 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TotW a_dMV P_DB Timestamp: Active Power magnitude of deadband value subEna Enable substitution Tot W deadband Cycl: Report interval (s), Db: In % of range, Int Db: In %s zeroDb Tot W zero deadband...
  • Page 245 Section 7 1MRS756793 E Logical node data model Table 171: RESCMMXU Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 246 Section 7 1MRS756793 E Logical node data model Table 172: RESVMMXU Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 247 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description d_dWYE U0_RMS_DB Quality: U0 RMS, magnitude of reported value U0_RMS_DB Timestamp: U0 RMS, magnitude of reported value subEna Enable substitution V RMS deadband res Cycl: Report interval (s), Db: In % of range, Int Db: In %s zeroDb...
  • Page 248 Section 7 1MRS756793 E Logical node data model LN type LN prefix LN class Function block name VPHMMXU (revision 0) VPH MMXU VPHMMXU Table 175: VPHMMXU Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850...
  • Page 249 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dWYE rangeC.lLim.f V low limit PhC Low limit (physical value) rangeC.llLim.f V low low Lim PhC Low Low limit (physical value) rangeC.max.f V maximum PhC Maximum value rangeC.min.f V minimum PhC...
  • Page 250 Section 7 1MRS756793 E Logical node data model Table 176: VPPMMXU Logical node data DO name DO type DA name Signal Mon/C Description a_dDEL rangeC.hhLim.f V Hi high Lim PhAB High High limit (physical value) rangeC.hLim.f V high limit PhAB High limit (physical value) rangeC.lLim.f V low limit PhAB...
  • Page 251: Harmonic Measurement Mhai

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dDEL U_DB_CA Timestamp: Phase C to A amplitude, magnitude of reported value subEna Enable substitution subEna Enable substitution subEna Enable substitution V deadband PhCA Cycl: Report interval (s), Db: In % of range, Int Db: In %s V deadband PhAB...
  • Page 252 Section 7 1MRS756793 E Logical node data model Table 177: CMHAI Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 253 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description ThdA f_dWYE cVal.mag.f 3SMNTHD_C Non-sliding 3s mean value of THD for phase C 3SMNTHD_C Quality: Non-sliding 3s mean value of THD for phase C 3SMNTHD_B Quality: Non-sliding 3s mean value of THD for phase B...
  • Page 254 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHAVal3 v2_dMV MAXH3 Quality: Max 3rd harmonic updated after exiting alarm state MAXH3 Timestamp: Max 3rd harmonic updated after exiting alarm state MaxHAVal4 v2_dMV mag.f MAXH4...
  • Page 255 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHAVal11 v2_dMV MAXH11 Quality: Max 11th harmonic updated after exiting alarm state MAXH11 Timestamp: Max 11th harmonic updated after exiting alarm state MaxHAVal12 v2_dMV mag.f MAXH12...
  • Page 256 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHAVal19 v2_dMV MAXH19 Quality: Max 19th harmonic updated after exiting alarm state MAXH19 Timestamp: Max 19th harmonic updated after exiting alarm state MaxHAVal20 v2_dMV mag.f MAXH20...
  • Page 257 Section 7 1MRS756793 E Logical node data model Table 178: VPPMHAI Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 258 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description HiHV v1_dSPS ALM_MN_H Timestamp: Alarm signal when harmonic RMS value is greater than limit HiVThd v1_dSPS stVal ALM_MN_THD Alarm signal when THD value is greater than limit ALM_MN_THD Quality: Alarm signal when THD...
  • Page 259 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHVVal3 v2_dMV MAXH3 Timestamp: Max 3rd harmonic updated after exiting alarm state MaxHVVal4 v2_dMV mag.f MAXH4 Max 4th harmonic updated after exiting alarm state MAXH4 Quality: Max 4th harmonic updated after exiting alarm state...
  • Page 260 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHVVal11 v2_dMV MAXH11 Timestamp: Max 11th harmonic updated after exiting alarm state MaxHVVal12 v2_dMV mag.f MAXH12 Max 12th harmonic updated after exiting alarm state MAXH12 Quality: Max 12th harmonic updated after exiting alarm state...
  • Page 261 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHVVal19 v2_dMV MAXH19 Timestamp: Max 19th harmonic updated after exiting alarm state MaxHVVal20 v2_dMV mag.f MAXH20 Max 20th harmonic updated after exiting alarm state MAXH20 Quality: Max 20th harmonic updated after exiting alarm state...
  • Page 262 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Quality: Mode status value parameter for 61850...
  • Page 263 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description HiVThd v1_dSPS ALM_MN_THD Quality: Alarm signal when THD value is greater than limit ALM_MN_THD Timestamp: Alarm signal when THD value is greater than limit HiVTdd v1_dSPS stVal...
  • Page 264 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHVVal7 v2_dMV MAXH7 Quality: Max 7th harmonic updated after exiting alarm state MAXH7 Timestamp: Max 7th harmonic updated after exiting alarm state MaxHVVal8 v2_dMV mag.f MAXH8...
  • Page 265 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description MaxHVVal15 v2_dMV MAXH15 Quality: Max 15th harmonic updated after exiting alarm state MAXH15 Timestamp: Max 15th harmonic updated after exiting alarm state MaxHVVal17 v2_dMV mag.f MAXH17...
  • Page 266: Sequence And Imbalance Msqi

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TddPhV v3_dWYE cVal.mag.f 3SMNTDD_B Non-sliding 3s mean value of TDD for phase B cVal.mag.f 3SMNTDD_C Non-sliding 3s mean value of TDD for phase C 3SMNTDD_C Quality: Non-sliding 3s mean value of TDD for phase C...
  • Page 267 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 a_dINS...
  • Page 268 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SeqA c_dSEQ I2_DB Timestamp: Negative sequence current amplitude, reported value I2_DB Timestamp: Negative sequence current amplitude, reported value subEna Enable substitution subEna Enable substitution Ps Seq A deadband Cycl: Report interval (s), Db: In % of range, Int Db: In %s...
  • Page 269 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description SeqV c_dSEQ rangeC.max.f Ps Seq voltage Max Maximum value rangeC.min.f Ps Seq voltage Min Minimum value cVal.mag.f U1_DB Positive sequence voltage amplitude, reported value rangeC.hhLim.f Ng Seq V Hi high Lim High High limit (physical value)
  • Page 270: Logical Nodes For Sensors And Monitoring

    Section 7 1MRS756793 E Logical node data model Logical nodes for sensors and monitoring 7.9.1 Circuit breaker monitoring SCBR LN type LN prefix LN class Function block name SSCBR (revision 1) S SCBR SSCBR Table 182: SSCBR Logical node data DO name DO type DA name...
  • Page 271 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RmnLifPhC v1_dINS CB_LIFE_C Quality: CB Remaining life phase CB_LIFE_C Timestamp: CB Remaining life phase C RsAccAPwr v1_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent...
  • Page 272 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description RsSprChaTm v1_dSPC Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check...
  • Page 273 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description LonTmAlm v1_dSPS stVal MON_ALM CB 'not operated for long time' alarm MON_ALM Quality: CB 'not operated for long time' alarm MON_ALM Timestamp: CB 'not operated for long time' alarm SprChaAlm v1_dSPS...
  • Page 274 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description TmmsOpn v2_dMV T_TRV_OP Timestamp: Travel time of the CB during opening operation TmsSprCha v2_dMV mag.f T_SPR_CHR The charging time of the CB spring T_SPR_CHR Quality: The charging time of the CB spring...
  • Page 275: Tap Changer Supervision Sltc

    Section 7 1MRS756793 E Logical node data model Table 183: TCSSCBR Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 276: Operation Time Counter Sopt

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Quality: Mode status value parameter for 61850 Timestamp: Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850...
  • Page 277 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 OpTmRs a_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850...
  • Page 278: Hot-Spot And Ageing Rate Monitoring Sptr

    Section 7 1MRS756793 E Logical node data model 7.9.4 Hot-spot and ageing rate monitoring SPTR LN type LN prefix LN class Function block name ARASPTR instance 1 (revision 0) SPTR HSARSPTR HSARLLN0 instance 1 (revision 0) LLN0 HSARSPTR HSARSPTR instance 1 (revision 0) HSAR SPTR HSARSPTR Table 186:...
  • Page 279 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 Table 188: HSARSPTR Logical node data (instance 1) DO name DO type DA name...
  • Page 280: Logical Nodes For Switchgear

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description HPToOilGra v2_dMV Quality: Hot spot to top oil gradient at rated load Timestamp: Hot spot to top oil gradient at rated load LoadRsvWrn v2_dMV mag.f LD_RSV_WRN...
  • Page 281 Section 7 1MRS756793 E Logical node data model Table 189: DAXCBR Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850...
  • Page 282 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description BlkOpn a_dSPC OP_BLKD Quality: Indication that the function is blocked for open commands OP_BLKD Timestamp: Indication that the function is blocked for open commands a_dSPS stVal...
  • Page 283: Switch Xswi

    Section 7 1MRS756793 E Logical node data model 7.10.2 Switch XSWI LN type LN prefix LN class Function block name DAXSWI (revision 0) DA XSWI DAXSWI Table 190: DAXSWI Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal...
  • Page 284 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description BlkOpn a_dSPC Oper.T Special block command value Oper.Test Special block command value Oper.Check Special block command value stVal OP_BLKD Indication that the function is blocked for open commands OP_BLKD Quality: Indication that the function...
  • Page 285: Logical Nodes For Further Power System Equipment

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description BlkUpd v1_dSPC Oper.origin.orIdent Special block command value Oper.ctlNum Special block command value Oper.T Special block command value Oper.Test Special block command value Oper.Check Special block command value stVal UPD_BLKD...
  • Page 286: Logical Nodes For Power Quality Events

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description BatHi a_dSPS stVal ST_UHIGH Start signal when battery voltage exceeds upper limit ST_UHIGH Quality: Start signal when battery voltage exceeds upper limit ST_UHIGH Timestamp: Start signal when battery voltage exceeds upper limit...
  • Page 287 Section 7 1MRS756793 E Logical node data model Table 192: PHQVVR Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 RsCnt a_dSPC Oper.ctlVal...
  • Page 288 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description DipStr d_dSPS stVal DIPST Voltage dip active DIPST Quality: Voltage dip active DIPST Timestamp: Voltage dip active SwlStr d_dSPS stVal SWELLST Voltage swell active SWELLST Quality: Voltage swell active SWELLST...
  • Page 289 Section 7 1MRS756793 E Logical node data model Table 193: PHQVVR Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status parameter for 61850...
  • Page 290 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description AMagPhA v2_dMV mag.f 1 Varn A PhA Record data of bank 1 for phase A current magnitude 1 Varn A PhA Quality: Record data of bank 1 for phase A current magnitude 1 Varn A PhA Timestamp: Record data of bank 1...
  • Page 291 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VVaTm2 v2_dMV 2 Varn Dur PhB Quality: Record data of bank 2 for phase B variation duration 2 Varn Dur PhB Timestamp: Record data of bank 2 for phase B variation duration VVaTm3 v2_dMV...
  • Page 292 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VVaTyp v7_dINS stVal 2 Variation type Record data of bank 2 for variation type 2 Variation type Quality: Record data of bank 2 for variation type 2 Variation type Timestamp: Record data of bank 2...
  • Page 293 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description VVa2 v2_dMV 3 Varn V PhB Quality: Record data of bank 3 for phase B voltage magnitude 3 Varn V PhB Timestamp: Record data of bank 3 for phase B voltage magnitude VVa3 v2_dMV...
  • Page 294: Voltage Unbalance Variation Qvub

    Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC stVal Mode status parameter for 61850 Quality: Mode status parameter for 61850 Timestamp: Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter...
  • Page 295 Section 7 1MRS756793 E Logical node data model Table 197: VSQVUB Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status value parameter for...
  • Page 296 Section 7 1MRS756793 E Logical node data model Table 199: VSQVUB Logical node data (instance 3) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Quality: Behaviour parameter for 61850 Timestamp: Behaviour parameter for 61850 c_dINC stVal Mode status value parameter for...
  • Page 297 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description v1_dSPC Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 stVal Reset status for IEC61850...
  • Page 298 Section 7 1MRS756793 E Logical node data model DO name DO type DA name Signal Mon/C Description d_dACD MN_UNB_AL Quality: Alarm active when 3 sec voltage unbalance exceeds the limit MN_UNB_AL Timestamp: Alarm active when 3 sec voltage unbalance exceeds the limit HiMnImbVal v2_dMV...
  • Page 299: Section 8 Glossary

    Section 8 1MRS756793 E Glossary Section 8 Glossary ACSI Abstract communication service interface Behavior BRCB Report control block Configured IED description Data attribute Data attribute Defines the name, format, range of possible values and representation of values while being communicated Data object Also known as DO.
  • Page 300 Section 8 1MRS756793 E Glossary IET600 Integrated Engineering Toolbox International Standard Organization Logical device Logical device zero (0) LHMI Local human-machine interface LLN0 Logical node zero (0) Logical node Logical device Also known as LD. Representation of a group of functions. Each function is defined as a logical node.
  • Page 304 — ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/relion © Copyright 2019 ABB. All rights reserved.

Table of Contents