Emc And Environmental Type Tests - Siemens RUGGEDCOM RS969 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS969:
Table of Contents

Advertisement

RUGGEDCOM RS969
Installation Guide
Test
MIL-STD 901D
MIL-STD-1275B
MIL-STD-1399
Section 7.3

EMC and Environmental Type Tests

The RUGGEDCOM RS969 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
EMC and Environmental Type Tests
Description
ESD
Enclosure Contact
Radiated RFI
Enclosure ports
Burst (Fast Transient)
DC Power ports
AC Power ports
Earth ground ports
Surge
DC Power ports
AC Power ports
Induced
(Conducted) RFI
DC Power ports
AC Power ports
Earth ground ports
Magnetic Field
Enclosure ports
Description
High Temperature Method 501.4 Procedure II Operational
Low Temperature Method 502.4 Procedure I Storage
Low Temperature Method 502.4 Procedure II Operational
Temperature Shock Method 503.4 Procedure I Storage
Acceleration Method 513.5 Procedure II
Salt Fog Method 509.4 Procedure I
Vibration Method 514.5
High Impact Shock Test
Power Quality
DC Magnetic Field Testing Section 070 Part 1
Enclosure Air
Signal ports
Signal ports
± 4 kV line-to-earth, ± 2 kV line-to-line
± 2 kV line-to-earth, ± 1 kV line-to-line
± 4 kV line-to-earth, ± 2 kV line-to-line
Signal ports
40 A/m continuous, 1000 A/m for 1 s
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
10V
10 V
10 V
10 V
Chapter 7
Certification
Severity
Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
43