Panasonic Aquarea B1 Planning And Installation Manual page 113

Air-to-water heat pumps split systems and compact systems
Table of Contents

Advertisement

Appendix
Menus
For installers
Menu
6.2
Cooling *
1,
*
2
Setting of different
temperatures for the cooling
mode.
*1 The system is preset for operation without a cooling function. The cooling function can be activated by an authorised installer or service partner.
*2 This display only appears if the cooling function is activated, i.e. if the cooling mode is available.
216
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Standard setting
Setting options /Display
T for heating mode
Temperature
difference for
5 °C
switching on the
heating again
Bivalence temp. E-heating element
Outside temperature
below which the
electric heating
0 °C
element can
be switched on
(bivalence point)
Water temperatures for cooling ON
and T for cooling ON.
Water temperature set-point for cooling
Setting of whether the
supply temperature is to
Heating
be calculated according
to cooling levels or to
be permanently set.
Water temperature set-point for cooling Heating
Entry of
X axis:
4 temperature values.
20 °C. 30 °C
(2 on the horizontal X
Y axis:
axis, 2 on the vertical
15 °C, 10 °C
Y axis)
• If a second cooling circuit is present, the 4 temperature values must also be given for
cooling circuit 2.
• "HC 1" and "HC 2" are not shown in the display if the system only has one heating
circuit (or cooling circuit).
Water temperature set-point for cooling Fixed value
Permanently set
10 °C
preliminary temperature
T for cooling mode
Temperature difference
5 °C
for switching on the
cooling.
Menu
6.3
Auto
Automatic switching from
heating to cooling mode or
from cooling to heating mode.
6.4
Hot water tank
Settings for the operation of
the hot water tank
• Only available if a connection
with the hot water tank is in
place.
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Standard setting
Setting options /Display
Outside temperatures for switching from
heating to cooling mode or from cooling to
heating mode.
Outside temp. for heating -> cooling /
Outside temp. for cooling -> heating
Outside temp. for heating -> cooling
Set outside temp. for
switching
15 °C
from heating to cooling
mode.
Outside temp. for cooling -> heating
Set outside temperature
for switching
10 °C
cooling to heating
mode.
Heating interval (max.) /
Hot water loading time (max.) /
Hot water switchon temp. difference /
Sterilisation
• The display shows 3 functions at the same time.
Heating interval (max.)
Maximum duration of
8:00
the heating interval
(in hours and minutes)
Hot water loading duration (max.)
Maximum duration of
1:00
the hot water interval
(in hours and minutes)
Hot water switch-on temp. difference
Temperature difference
-8 °C
for reloading of the hot
water tank
Appendix
217