Connecting The Condensation Outflow Hose - Panasonic Aquarea B1 Planning And Installation Manual

Air-to-water heat pumps split systems and compact systems
Table of Contents

Advertisement

Installation

6.7.2.1 Connecting the condensation outflow hose

Indoor units
Carry out the following steps to connect the outflow hose to the condensation outflow of the
indoor unit:
1. Assemble the supplied outlet bend with seal on the condensation outflow on the under-
side of the indoor unit, as shown in the illustrations below.
2. Push the hose over the outlet bend.
3. Ensure that the outflow hose is seated firmly. Use a hose clip to attach the hose, if neces-
sary (to be provided on site).
4. Lay the outflow hose in a constant downward alignment into a suitable collection fixture
for the condensation (to be provided on site).
Combination Hydro-module H-Generation
Detail view from below
2
3
Outdoor units
!
IMPORTANT
Also use the following instructions at the time of installation of the condensation outflow hose on
the outdoor unit:
● When using the outlet bend, the outdoor unit should be mounted on a sub-base at
least 50 mm in height.
● For installation of the outdoor unit on a foundation, the installation method with a
strip foundation and gravel filling is recommended
unit, p.
92). For a safe drainage of condensation water, even at outside tempera-
tures below 0 °C, a drain pipe is recommended, reaching into the frost-free area of
the underground.
168
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Hydro-module H-Generation
Detail view from below
1
1
2
3
1 Condensation outlet
2 Sealing washer
3 Outlet bend
(→ 5.2.2.3 Securing the outdoor
Carry out the following steps to connect the outflow hose to the condensation outflow of the
outdoor unit:
1. Assemble the supplied outlet bend with seal on the condensation outflow on the under-
side of the outdoor unit, as shown in the figures below.
2. Seal the openings on the underside of the outdoor unit (model-dependent number: 7 or 8)
using the supplied rubber sealing caps.
3. Push the hose over the outlet bend.
4. Ensure that the outflow hose is seated firmly. Use a hose clip to attach the hose, if neces-
sary (to be provided on site).
5. Lay the outflow hose in a constant downward alignment. For large outflow hose lengths,
you may want to use a metal support (provided on site) to prevent the hose from bending.
Detail view from below
1
Compact devices
Carry out the following steps to connect the outflow hose to the condensation outflow of the
compact device:
1. Slide the outflow hose onto the condensation outlet socket on the compact device.
2. Ensure that the outflow hose is seated firmly. Use a hose clip to attach the hose, if neces-
sary (to be provided on site).
3. Lay the outflow hose in a constant downward alignment. For large outflow hose lengths,
you may want to use a metal support (provided on site) to prevent the hose from bending.
View from below
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Installation
2
1 Condensation outlet
2 Outlet bend
3 Openings
(7 or 8, depending on model)
4 Rubber seal caps
3
4
1 Condensation outlet
1
169