Panasonic Aquarea B1 Planning And Installation Manual page 59

Air-to-water heat pumps split systems and compact systems
Table of Contents

Advertisement

Planning
For the hydro-module WH-SDC12H6E5, WH-SDC16H6E5:
● Mains supply 1 of this device fulfils EN/IEC 61000-3-12, provided that the short-cir-
cuit power S
at the transfer point of the energy provider to the operator is greater
k
than or equal to 2200 kW. The installer or operator of the device is, therefore,
responsible for ensuring, in case a consultation with the EVU is needed, that the
device is only connected, if the short-circuit power S
2200 kW.
● Mains supply 1 of the device fulfils ICE/ EN 61000-3-11 and is to be connected to
a suitable voltage source, which has a current rating ≥100 A per phase. Connect
to the EVU to ensure that the current rating at the transfer point is sufficient for the
device.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-12.
● Mains supply 2 of the device fulfils IEC/EN 61000-3-11 and is to be connected to a
suitable voltage source, which has a maximum permissible system impedance of
Z
= 0.271 Ω at the transfer point. Connect to the EVU to ensure that the mains
max
supply 2 is only connected to a grid with the maximum of this impedance.
For the hydro-module WH-SXC09H3E5, WH-SXC12H6E5:
● Mains supply 1 of this device fulfils EN/IEC 61000-3-12, provided that the short-cir-
cuit power S
at the transfer point of the energy provider to the operator is greater
k
than or equal to 1700 kW. The installer or operator of the device is, therefore,
responsible for ensuring, in case a consultation with the EVU is needed, that the
device is only connected, if the short-circuit power S
1700 kW.
● Mains supply 1 of the device fulfils ICE/ EN 61000-3-11 and is to be connected to
a suitable voltage source, which has a current rating ≥100 A per phase. Connect
to the EVU to ensure that the current rating at the transfer point is sufficient for the
device.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-12.
● Mains supply 2 of the device fulfils IEC/EN 61000-3-11 and is to be connected to a
suitable voltage source, which has a maximum permissible system impedance of
Z
= 0.271 Ω at the transfer point. Connect to the EVU to ensure that the mains
max
supply 2 is only connected to a grid with the maximum of this impedance.
For the hydro-modules WH-SDC12H9E8, WH-SDC16H9E8, WH-SXC12H9E8,
WH-SXC16H9E8, WH-SQC12H9E8 and WH-SQC16H9E8:
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-2.
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-3 and can be connected to
the current supply grid.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-2.
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-3 and can be connected to
the current supply grid.
112
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
is greater than or equal to
k
is greater than or equal to
k
L N
L N
L
N
L
N
Compact systems
1
1
1
1
Models
Mains connection 1
L N
L N
L
N
L
N
1
1
1
1
Phases
Max. current
consumption (A)
WH-MDC05H3E5
1
19.5
WH-MDC07H3E5
1
20.5
WH-MDC09H3E5
1
22.9
WH-MXC09H3E5
1
25.0
WH-MXC12H6E5
1
29.0
WH-MHF09G3E5
1
28.5
WH-MHF12G6E5
1
29.0
FI protection switch and mains connections
FI protection
switch
Mains connections
Models
Mains connection 1
Phases
Max. current
consumption (A)
WH-MXC09H3E8
3
14.7
WH-MHF09G3E8
3
14.5
FI protection switch and mains connections
FI protection
switch
Mains connections
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Mains connection 2
Max. power
Phases
Max. current
consumption (kW)
consumption (A)
consumption (kW)
4.26
1
13.0
4.48
1
13.0
5.01
1
13.0
5.41
1
13.0
6.27
1
26.0
6.09
1
13.0
6.20
1
26.0
N
L
L
L
L
L
L
A1
A2
A1
A3
A2
A3
L N
L
N
1
Terminals on compact device
1
1
L N
L
N
L
Terminals on disconnector of the mains connection
L
L
L
L
N
L
2
1
1
A1
A2
A1
A3
A2
A3
Mains connection 1 Mains connection 2
Mains connection 2
Max. power
Phases
Max. current
consumption (kW)
consumption (A)
consumption (kW)
9.85
1
13.0
9.67
1
13.0
N
Terminals on compact device
L
L
L
L
N
1
A1
A2
A3
Terminals on disconnector of the mains connection
L
L
L
N
L
N
2
A1
A2
A3
Mains connection 1
Mains connection 2
Planning
Max. power
3.0
3.0
3.0
3.0
6.0
3.0
6.0
N
L
N
L
N
N
L
N
L
N
Max. power
3.0
3.0
113