3-2. Use R410A exclusive cylinder only.
When charging with a refrigerant cylinder, use an
electronic scale for charging refrigerant. In this
case, if the volume of refrigerant in the cylinder
becomes less than 20% of the fully-charged
amount, the composition of the refrigerant starts
to change. Thus, do not use the refrigerant if the
amount in the charging cylinder is less than 20%.
Also, charge the minimum necessary amount to
the charging cylinder before using it to charge the
air conditioning unit.
Panasonic̲PAC-i̲IndoorUnit̲US-le5   5
Panasonic̲PAC-i̲IndoorUnit̲US-le5   5
Configuration and characteristics of cylinders
Liquid
Single valve
Charge liquid refrigerant with
cylinder in up-side-down position.
Fig. 1
Single valve (with siphon tube)
Charge with cylinder in normal position.
Fig. 2
5
Valve
Valve
Liquid