[5-1 Dipswitch Functions and Factory Settings ]

5-1

Dipswitch Functions and Factory Settings

5 Control
5-1-1

Outdoor Unit Switch Functions and Factory Settings

(1) Control board
Switch
SWU
1-2
Unit address setting
1
Centralized control switch
Deletion of connection infor-
2
mation
3
SW5
4
5
6
7
8
1
COP priority setting (at low
2
outside temperature)
3
Model setting (outdoor unit/
4
high static pressure setting)
Model setting (outdoor unit/
5
high static pressure setting)
SW6
6
Performance-priority/low-
7
noise mode setting
Low-noise mode/step demand
8
switching
9
Self-diagnosis monitor display
10
/ SW4 function setting mode
switching
BS_05_E
Function according to switch setting
Function
Set to 00 or 51-100 with the dial switch
Without connection to
the centralized control-
ler
Normal control
-
-
-
-
-
-
-
Heating COP priority
mode
-
Function depends on the setting combination
with the SW6-5 setting (Note 5).
(Factory setting: OFF)
Function depends on the setting combination
with the SW6-4 setting (Note 5).
(Factory setting: OFF)
-
Performance-priority
mode (Note 2)
Low-noise mode (Note
3)
-
Self-diagnosis monitor
display
OFF
ON
With connection to the
centralized controller
Deletion
Preset before shipment
(Varies with unit type and model)
-
-
Heating capacity priori-
ty control mode
-
-
-
-
Quiet-priority mode
(Note 4)
Step demand mode
-
-
SW4 function setting
mode
Switch setting timing
Before power on
Before power on
Before power on
-
Before power on
-
Before power on
Before power on
-
Anytime after power on
Before power on
-
Anytime after power on
1
chapter 5 -