Mitsubishi Electric 800 Series Instruction Manual page 144

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Item
Character system
Start bit
Stop bit length
Communication
specifications
Parity check
Error check
Terminator
Time delay setting
 Outline
• The MODBUS communication protocol was developed by Modicon for programmable controllers.
• The MODBUS protocol uses exclusive message frames to perform serial communication between a master and slaves.
These exclusive message frames are provided with a feature called "functions" that allows data to be read or written. These
functions can be used to read or write parameters from the inverter, write input commands to the inverter or check the
inverter's operating status, for example. This product classifies the data of each inverter into holding register area (register
address 40001 to 49999). The master can communicate with inverters (slaves) by accessing pre-assigned holding register
addresses.
NOTE
• There are two serial transmission modes, the ASCII (American Standard Code for Information Interchange) mode and the RTU
(Remote Terminal Unit) mode. However, this product supports only the RTU mode, which transfers 1 byte data (8 bits) as it
is. Also, only communication protocol is defined by the MODBUS protocol. Physical layers are not stipulated.
 Message format
• Data check time
Item
Monitoring, operation command, frequency setting (RAM)
Parameter read/write, frequency setting (EEPROM)
Parameter clear / All parameter clear
Reset command
• Query
A message is sent to the slave (the inverter) having the address specified by the master.
• Normal response
After the query from the master is received, the slave executes the request function, and returns the corresponding normal
response to the master.
• Error Response
When an invalid function code, address or data is received by the slave, the error response is returned to the master.
This response is appended with an error code that indicates the reason why the request from the master could not be
executed.
This response cannot be returned for errors, detected by the hardware, frame error and CRC check error.
• Broadcast
The master can broadcast messages to all slaves by specifying address 0. All slaves that receive a message from the
master execute the requested function. With this type of communication, slaves do not return a response to the master.
Binary (fixed at 8 bits)
1 bit
Select from the following three types:
No parity check, stop bit length 1 bit / 2 bits (depends on the setting of Pr.119)
Odd parity check, stop bit length 1 bit
Even parity check, stop bit length 1 bit
CRC code check
Not available
Not available
Query communication
Programmable controller
(Master)
Inverter (slave)
Broadcast communication
Programmable controller
(Master)
Inverter (slave)
Check time
Less than 12 ms
Less than 30 ms
Less than 5 s
No reply
Description
Inverter response time
(Refer to the following table for the
data check time)
Query Message
Response Message
Data absence time
(3.5 bytes or more)
Query Message
Related parameter
Pr.119
Pr.120
No Response
3. RS-485 Communication
3.5 MODBUS RTU
1
2
3
4
5
6
7
8
9
10
143