Mitsubishi Electric 800 Series Instruction Manual page 79

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• Product profile
Register
44001
Model (1st and 2nd characters)
44002
Model (3rd and 4th characters)
44003
Model (5th and 6th characters)
44004
Model (7th and 8th characters)
44005
Model (9th and 10th characters)
44006
Model (11th and 12th characters)
44007
Model (13th and 14th characters)
44008
Model (15th and 16th characters)
44009
Model (17th and 18th characters)
44010
Model (19th and 20th characters)
44011
Capacity (1st and 2nd characters)
44012
Capacity (3rd and 4th characters)
44013
Capacity (5th and 6th characters)
NOTE
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
 ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE
STATEMENT (NORMATIVE)
(This annex is part of this Standard and is required for its use.)
BACnet Protocol Implementation Conformance Statement
Date: 9th December 2019
Vendor Name: Mitsubishi Electric Corporation
Product Name: Inverter
Product Model Number: (FR-E800 series)
Application Software Version: 8650*
Firmware Revision: 1.00
BACnet Protocol Revision: 19
Product Description:
BACnet Standardized Device Profile (Annex L):
BACnet Cross-Domain Advanced Operator Workstation (B-XAWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Workstation (B-OWS)
BACnet Operator Display (B-OD)
BACnet Advanced Life Safety Workstation (B-ALSWS)
BACnet Life Safety Workstation (B-LSWS)
BACnet Life Safety Annunciator Panel (B-LSAP)
BACnet Advanced Access Control Workstation (B-AACWS)
BACnet Access Control Workstation (B-ACWS)
BACnet Access Control Security Display (B-ACSD)
BACnet Building Controller (B-BC)
78
2. Ethernet Communication
2.8 BACnet/IP
Definition
Read/write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Remarks
The model name can be read in ASCII code.
"H20" (blank code) is set for blank area.
Example) FR-E820-EPA:
H46, H52, H2D, H45, H38, H32, H30, H2D, H45, H50, H41,
H20...H20
The inverter rated capacity can be read in ASCII code.
Data read is displayed in increments of 0.1 kW (rounded down to
one decimal place).
"H20" (blank code) is set for blank area.
Example) 0.75K: "
7" (H20, H20, H20, H20, H20, H37)