Chapter 7 Maintenance

7.1 Checking the LEDs

The operation of CIF module can be diagnosed by checking the LEDs.
LED
CH1
The diagnosis procedure when there is an error is as follows:
(1) CH1-LED is not lit at receive timing.
(2) CH1-LED is lit but data cannot received
(3) CH1-LED is not lit at transmit timing.
6F8C0843
Function
Lit when transmitting or receiving
・ Check that the RXD signal line, SG line are connected.
・ Check that the connected device is operating normally.
・ Check the controller program to determine whether the receive program is
operating.
・ Check the status information to see if there is receive error.
・ If there is receive error, check whether the baud rate, parity, data bit length,
and stop bit setting made with the switches on the front matches the setting of
the connected device.
・ Check the controller program to determine that the transmit program is
operating.
・ If status information indicates an error, check that the trailing code of the
transmit data matches the trailing code set in the CIF module.