Installing U32 Enhanced Subrack Ground Cable
Ground point 1:
Connect one end of the subrack ground cable to the ground screw at the top of the subrack, and connect
the other end to an appropriate ground screw located on the right-side cabinet column.
M6
4.90±0.49 N· m
Installing U32 Enhanced Subrack Ground Cable
NOTE
The U32 enhanced subrack has two ground screws,
which are commonly used at ground point 1. If an air
deflector is installed in the upper part of the subrack, use
ground point 2.
Ground point 2:
Connect one end of the subrack ground cable to the ground
bolt on the side of the U32 enhanced subrack, and the other
end to an appropriate ground bolt located on the right-side
cabinet column.
58
M5
2#screwdriver
2.94 ± 0.29 N· m