3.Analog Output Configuration Example - ABB REF 54 Series Technical Reference Manual, General

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

REF 54_
5.1.10.3.
62
Feeder Terminal
Technical Reference Manual, General
The output behavior when the value attribute is outside the defined limits is as
follows:
Output range
Value of AO#
0...20 mA
>20
0...20
<0
4...20 mA
>20
4...20
<4
Note that the output is also forced to 0 mA on the 4...20 mA range when the value
is below the low limit. This behavior can be used to indicate a fault to the receiver.
Analog output configuration example
The analog outputs are supported in the Relay Configuration Tool by the
MEAO1...MEAO4 analog output function blocks. As an example, to display the
measured value of neutral current on an analog gauge, the neutral current
measurement block MECU1A is connected to MEAO1, which in turn is connected
to the RTD1_6_AO1 global variable. The output invalid signal RTD1_6_AO1IV is
connected to the MMIALAR1 function block to achieve a visual indication of a
fault. The MEAO# function blocks contain the parameters necessary for scaling the
measured value to fit the selected output range. The MEAO# function blocks also
limit the output change frequency to achieve a tolerable system load.
Fig. 5.1.10.3.-1 Analog output configuration example
Output current
Invalidity attribute AO#IV
20 mA
0...20 mA
0 mA
20 mA
4...20 mA
0 mA
1MRS750527-MUM
TRUE
FALSE
TRUE
TRUE
FALSE
TRUE
meaox1