11.Lon Inputs And Outputs Via A Lon Bus - ABB REF 54 Series Technical Reference Manual, General

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

REF 54_
5.1.13.10.
80
Feeder Terminal
Technical Reference Manual, General
LON inputs and outputs via a LON bus
The REF 54_ feeder terminal offers up to 32 freely programmable LON inputs and
outputs on the LON bus. The inputs and outputs use the LonMark Standard network
variable (NV type 83 = SNVT_state) for sending and receiving process data. The
LON inputs and outputs are accessible in the feeder terminal configuration and can
be freely used for different types of data transfer between REF 54_ feeder terminals
and other devices that are able to communicate using the network variable of type
SNVT_state.
Fig. 5.1.13.10.-1Principle of connecting LON inputs and outputs to logic functions
of the feeder terminal
Each SNVT_state network variable can be used to communicate either an integer
value in the range of 0-65535 or up to 16 Boolean values as a binary coded number.
The type conversion function BOOL2INT is useful for packing and INT2BOOL for
unpacking the binary coded variables. Each bit indicates the state of the Boolean
value with, for example, the following interpretations:
0
1
off
on
inactive
active
disabled
enabled
low
high
false
true
normal
alarm
The communication inputs and outputs are seen in the relay configuration tool as
global variables:
Category
Communication inputs (sinks)
Communication outputs (sources) COMM_OUTx
1) Where x is a number from 1 to 32. Similar names are used in the LON Network Tool.
Name
Datatype
UINT
1)
COMM_INx
BOOL
1)
COMM_INxIV
1)
UINT
1MRS750527-MUM
lonlog_b
Purpose
Input value
Input invalidity flag, FALSE
indicates a valid state
Output value

Hide quick links: