3.4 Configuration of
inputs and outputs
Installation and commissioning
When communicating via the LON port, the settings are made with the
LNT, LON Network Tool. The settings are shown on the built-in MMI at:
Configuration
LON Comm
From this menu, it is also possible to send the "ServicePinMessage" to the
LNT.
For
further
(1MRK 580 142-XEN).
The terminal has a default configuration for all functions, that is, there is a
default internal wiring of the terminal. All input and output contacts are
also wired to functions in the terminal.
You can change the configuration on the built-in MMI or via PC/SMS,
either with or without the CAP 531 configuration tool. On the built-in
MMI, the configuration is done at:
Configuration
Function Inputs, Slotnn-XXXyy
For REC 561, all configuration is performed with CAP 531, and no con-
figuration can be changed on the built-in MMI.
You can select the binary outputs from a signal list where the signals are
grouped under their function names. You can also specify a user-defined
name for each input and output signal.
When downloading a configuration to the terminal with the CAP 531 con-
figuration tool, the terminal is automatically set in configuration mode.
When the terminal is set in configuration mode, all functions are blocked.
The yellow LED of the terminal flashes, and the green LED is lit while the
terminal is in configuration mode.
When downloading ends, the terminal is automatically set in normal
mode.
instructions,
see
Remote
1MRK 580 166-XEN
Page
3 - 11
communication