3 Setting and configuration

3.1 Built-in man machine
interface (MMI)

3.2 Front Communication

Installation and commissioning
dark grey for glass). Transmitter fibre contacts (grey or black) must be
plugged likewise into transmitter sockets (grey or black).
Note: Plug the correct fibre contact into the correct socket.
Fibre optical cables are sensitive to mechanical damages. Never bend
them. As for the curvature radius, these minimum values are valid:
• 5 cm radius for plastic fibre
• 15 cm radius for glass fibre
When the optical fibre is to be connected or disconnected, the termination,
and not the optical fibre must be used for pulling.
In case the optical fibre is too long and cable straps must be used, the
cable strap must not be applied too hard. Always leave some space
between the optical fibre and the cable strap.
The Serial communication modules are inserted into slots on the Main
processing module. There are four different types of cards — with plastic
connections for SPA, with plastic connections for LON, with glass con-
nection for SPA, with glass connection for LON. SPA communication can
only be applied with a module intended for SPA inserted in the SPA slot,
which is the upper slot (X13) on the Main processing module. In the same
way, LON communication can only be applied with a module intended for
LON, inserted in the lower slot (X15).
All settings and configuration can be made in these ways:
• Locally, via the built-in, man-machine interface (MMI) module
• Locally, on a PC via the optical front connector, using SMS (and
possibly CAP 531) in the PC
• Locally or remotely, via one of the ports on the rear (using SMS,
CAP 531 or SCS).
Note that in REC 561, all configuration is performed with CAP 531.
The setting access on the built-in MMI can be blocked by the binary input
signal MMI--BLOCKSET. When this signal is active, the LEDs can still
be cleared from the front.
When a PC is used for connection to the front, you need the SMS-BASE
and SM/REx 5xx, (SM/REL 531 for REL 531 etc.). (For the collection of
disturbances to a front connected PC, RECOM is not required because all
necessary functionality is built in to SM/REx 5xx.) For configuration,
CAP 531 can be used with SMS.
You use a special cable for connecting your PC to the front of the termi-
nal. This can be ordered from ABB Network Partner, order No.
1MKC 950 001-1. It is plugged into the optical contact on the left side of
1MRK 580 166-XEN