3.2.4 BLKCON

3.2.5 Communication
between modules
Apparatus control
BLKCON is used for blocking of functions in a bay and in an apparatus
control program. BLKCONL (x=1) contains one blocking function and
BLKCONK (x=1, 2 and 3) contains three blocking functions. The block-
ing function can be controlled with both steady and pulse signals. The
functionality can be represented by logic as in the Fig. 10 below.
BLK_x_1
BLK_x_2
BLK_x_3
BLKCMDx
DBLCMDx
BYPASSx
Fig. 10
The function of BLKCON represented by logic
Fig. 11 is used as starting-point when explaining the signal flow between
the different function block in the apparatus-control function. The control
program in Fig. 11 handles one bay, which includes two apparatuses. The
detailed connections between the modules can be seen in the type solu-
tions in the "Configurations" on page 25.
1
Apparatus 1
2
COMCON
Apparatus 2
COMCON
Fig. 11
The signal flow between different modules in a bay
≥1
S
R
Bay control
4
BLKCON
BAYCON
3
5
6
1MRK 580 150-XEN
Page
6 - 23
BLK_OUTx
&
x = 1,2, or 3
(X80150-10)
SWICON
BLKCON
SWICON
BLKCON
(X80150-11)