ABB REC 561 User Manual page 482

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
Interlocking
Table 8: Output signals for A1A2_BS
OUT:
IHxx-Q0OPREL
IHxx-Q0OPITL
IHxx-Q0CLREL
IHxx-Q0CLITL
IHxx-Q11REL
IHxx-Q11ITL
IHxx-Q12REL
IHxx-Q12ITL
IHxx-Q51REL
IHxx-Q51ITL
IHxx-Q52REL
IHxx-Q52ITL
IHxx-A1A2OPTR
IHxx-A1A2CLTR
IHxx-Q11OPTR
IHxx-Q11CLTR
IHxx-Q12OPTR
IHxx-Q12CLTR
IHxx-VPA1A2TR
IHxx-VPQ11TR
IHxx-VPQ12TR
1MRK 580 151-XEN
DESCRIPTION:
Opening of Q0 is allowed
Opening of Q0 is forbidden
Closing of Q0 is allowed
Closing of Q0 is forbidden
Switching of Q11 is allowed
Switching of Q11 is forbidden
Switching of Q12 is allowed
Switching of Q12 is forbidden
Switching of Q51 is allowed
Switching of Q51 is forbidden
Switching of Q52 is allowed
Switching of Q52 is forbidden
No bus coupler connection between bus
section A1 and A2
Bus coupler connection between bus sec-
tion A1 and A2
Signal is 1 if Q11 is open
Signal is 1 if Q11 is closed
Signal is 1 if Q12 is open
Signal is 1 if Q12 is closed
Switch status of Q0, Q11 and Q12 are valid
(open or closed)
Switch status of Q11 is valid (open or
closed)
Switch status of Q12 is valid (open or
closed)
Page