4 Commissioning

Installation and commissioning
Before any test occurs, set the terminal to test mode. This can be done on
the built-in MMI at:
Test
Test Mode
Operation
Test/Mode/Operation = On sets the terminal in test mode, but this is not
activated until this setting has been saved and the yellow LED starts to
flash. The test mode can also be activated via a binary input connected
to TEST-INPUT. So select the Operation above to BinInput in that case.
When TestMode is set to On (Test/Mode/Operation = On), the yellow
LED flashes and the setting of the Disturbance report parameters have this
effect:
On
Off
Off
On
Off
On
On
On
On
or
Off
ABB Network Partner AB
Then the results are...
• Disturbances are not stored.
• LED information is not displayed on the
MMI and not stored.
• No disturbance summary is scrolled on the
MMI.
• Disturbances are not stored.
• LED information (yellow - start, red - trip)
are displayed on the built-in MMI but not
stored in the terminal.
• Disturbance summary is scrolled automati-
cally on the built-in MMI for the two latest
recorded disturbances, until cleared. The
information is not stored in the terminal.
• The disturbance report works as in normal
mode.
• Disturbances are stored. Data can be read
from the built-in MMI, a front-connected
PC, or SMS.
• LED information (yellow - start, red - trip) is
stored.
• The disturbance summary is scrolled auto-
matically on the built-in MMI for the two lat-
est recorded disturbances, until cleared.
• All disturbance data that is stored during
test mode remains in the terminal when
changing back to normal mode.