7.3.4 SWICONB
Table 26: Setting table for SWICONB
PARAMETER: SETTING RANGE: DESCRIPTION:
T_POSERR
T_POL
T_SEL
T_START
T_PULSE
7.3.5 SWICONC
Table 27: Setting table for SWICONC
PARAMETER: SETTING RANGE: DESCRIPTION:
T_POSERR
T_PULSE
T_SEL
T_START
Apparatus control
0.0-200.0 s
Allowed time for middle position. To be set
from CAP 531
0.0-200.0 s
Time parameter for pole discordance.
Allowed time to have discrepancy between
the poles. To be set from CAP 531
0.0-200.0 s
Allowed time from selection to feedback
select. To be set from CAP 531
0.0-200.0 s
Allowed time from execute to position indi-
cation change. To be set from CAP 531
0.0-200.0 s
Time parameter for command output pulse
length. T_PULSE = 0 gives a steady com-
mand output signal. To be set from CAP
531
0.0-200.0 s
Allowed time for middle position. To be set
from CAP 531
0.0-200.0 s
Time parameter for command output pulse
length. T_PULSE = 0 gives a steady com-
mand output signal. To be set from CAP
531
0.0-200.0 s
Allowed time from selection to feedback
select. To be set from CAP 531
0.0-200.0 s
Allowed time from execute to position indi-
cation change. To be set from CAP 531