5.2 Check that the
protection does not
trip when set passive
5.3 Check that the
protection can be
started from all start
inputs
5.4 Check that the retrip
function works
Breaker-failure protection
MMI submenu:
Settings
Functions
Group n
If the settings are changed to speed up times during the tests, they
must later be reset and verified.
2.1
Set operation = Off.
2.2
Apply a stationary current over the set value.
2.3
Apply a start pulse to BFP--STL1.
2.4
Verify that neither retrip nor back-up trip is achieved.
3.1
Set RetripType = No I>check, I> = 100% I
3.2
Apply a stationary three-phase current over the set value.
3.3
Apply a start pulse to BFP--STL1.
3.4
Verify that retrip in phase L1 is achieved.
3.5
Apply a stationary current over the set value.
3.6
Apply a start pulse to BFP--ST3PH.
3.7
Verify that all three retrips are achieved.
4.1 No retrip function
4.1.1 Set RetripType = Retrip Off and I> = 100% I
4.1.2 Apply a stationary three-phase current over the set value.
4.1.3 Apply a start pulse to BFP--STL1.
4.1.4 Verify that retrip in phase L1 is not achieved.
4.2 Retrip function with current check
4.2.1 Set RetripType = I> check, t1 = 100 ms and I> = 100% I
4.2.2 Apply a stationary three-phase current over the set value.
4.2.3 Apply a start pulse to BFP--STL1.
4.2.4 Verify that retrip is achieved.
4.3 Retrip function without current check
4.3.1 Set RetripType = No I> check, t1 = 100 ms and I> = 100% I
4.3.2 Apply a stationary three-phase current over the set value.
4.3.3 Apply a start pulse to BFP--STL1.
4.3.4 Verify that retrip is achieved.
1MRK 580 171-XEN
Breaker Failure
and t1 = 50 ms.