3 Configuration
Command function
input time is set a little bit longer than the interval time set on the Event
function block (see Event function, (1MRK 580 140-XEN)). If INTER-
VAL=0, then VALID will be 1, that is, not applicable.
For REL 531, the configuration of the signal outputs of the Single Com-
mand function block to the inputs of the configuration logic circuits is
made in the built-in MMI under the menu:
Configuration
FunctionInputs
AND (OR, Timer, Pulse, INV, SR)
Command
The signal outputs of the command function can, of course, also be con-
nected directly to the binary outputs of the terminal or to built-in functions.
MMI tree for configuration to binary outputs:
Configuration
Slotxx-IOMy (BOMy)
Command
MMI tree for configuration to a built-in function:
Configuration
FunctionInputs
Function n
Command
The configuration of the signal outputs of the Single Command function
and Multiple Command function in REC 561 is made by the CAP 531 con-
figuration tool.
ABB Network Partner AB
Version 1.0-00