ABB REC 561 User Manual page 492

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
6.2.12BH_LINE_B
Interlocking
Table 22: Output signals for BH_CONN
OUT:
IKxx-Q51REL
IKxx-Q51ITL
IKxx-Q52REL
IKxx-Q52ITL
Table 23: Input signals for BH_LINE_B
IN:
IMxx-Q0_OP
IMxx-Q0_CL
IMxx-Q6_OP
IMxx-Q6_CL
IMxx-Q2_OP
IMxx-Q2_CL
IMxx-Q51_OP
IMxx-Q51_CL
IMxx-Q52_OP
IMxx-Q52_CL
IMxx-Q53_OP
IMxx-Q53_CL
IMxx-Q9_OP
IMxx-Q9_CL
IMxx-Q8_OP
IMxx-Q8_CL
IMxx-CQ0_OP
IMxx-CQ0_CL
IMxx-CQ62_OP
IMxx-CQ62_CL
IMxx-CQ51_OP
IMxx-CQ51_CL
IMxx-CQ52_OP
IMxx-CQ52_CL
IMxx-Q25_OP
1MRK 580 151-XEN
DESCRIPTION:
Switching of Q51 is allowed
Switching of Q51 is forbidden
Switching of Q52 is allowed
Switching of Q52 is forbidden
DESCRIPTION:
Signal is 1 if Q0 is open
Signal is 1 if Q0 is closed
Signal is 1 if Q6 is open
Signal is 1 if Q6 is closed
Signal is 1 if Q2 is open
Signal is 1 if Q2 is closed
Signal is 1 if Q51 is open
Signal is 1 if Q51 is closed
Signal is 1 if Q52 is open
Signal is 1 if Q52 is closed
Signal is 1 if Q53 is open
Signal is 1 if Q53 is closed
Signal is 1 if Q9 is open
Signal is 1 if Q9 is closed
Signal is 1 if Q8 is open
Signal is 1 if Q8 is closed
Signal is 1 if Q0 in module BH_CONN is
open
Signal is 1 if Q0 in module BH_CONN is
closed
Signal is 1 if Q62 in module BH_CONN is
open
Signal is 1 if Q62 in module BH_CONN is
closed
Signal is 1 if Q51 in module BH_CONN is
open
Signal is 1 if Q51 in module BH_CONN is
closed
Signal is 1 if Q52 in module BH_CONN is
open
Signal is 1 if Q52 in module BH_CONN is
closed
Signal is 1 if Q25 on busbar B is open
Page
6 - 207

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents