ABB REC 561 User Manual page 486

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
6.2.8 DB_LINE
Interlocking
Table 14: Output signals for DB_BUS_A
OUT:
IBxx-Q52ITL
IBxx-Q1OPTR
IBxx-Q1CLTR
IBxx-VPQ1TR
Table 15: Input signals for DB_LINE
IN:
IAxx-Q01_OP
IAxx-Q01_CL
IAxx-Q02_OP
IAxx-Q02_CL
IAxx-Q61_OP
IAxx-Q61_CL
IAxx-Q51_OP
IAxx-Q51_CL
IAxx-Q52_OP
IAxx-Q52_CL
IAxx-Q62_OP
IAxx-Q62_CL
IAxx-Q54_OP
IAxx-Q54_CL
IAxx-Q55_OP
IAxx-Q55_CL
IAxx-Q9_OP
IAxx-Q9_CL
IAxx-Q53_OP
IAxx-Q53_CL
IAxx-Q8_OP
IAxx-Q8_CL
IAxx-VOLT_OP
IAxx-VOLT_CL
IAxx-Q9EX1
IAxx-Q9EX2
IAxx-Q9EX3
1MRK 580 151-XEN
DESCRIPTION:
Switching of Q52 is forbidden
Signal is 1 if Q1 is open
Signal is 1 if Q1 is closed
Switch status of Q1 is valid (open or closed)
DESCRIPTION:
Signal is 1 if Q01 is open
Signal is 1 if Q01 is closed
Signal is 1 if Q02 is open
Signal is 1 if Q02 is closed
Signal is 1 if Q61 is open
Signal is 1 if Q61 is closed
Signal is 1 if Q51 is open
Signal is 1 if Q51 is closed
Signal is 1 if Q52 is open
Signal is 1 if Q52 is closed
Signal is 1 if Q62 is open
Signal is 1 if Q62 is closed
Signal is 1 if Q54 is open
Signal is 1 if Q54 is closed
Signal is 1 if Q55 is open
Signal is 1 if Q55 is closed
Signal is 1 if Q9 is open
Signal is 1 if Q9 is closed
Signal is 1 if Q53 is open
Signal is 1 if Q53 is closed
Signal is 1 if Q8 is open
Signal is 1 if Q8 is closed
There is no voltage on the line and no fuse
failure
There is voltage on the line and or a VT
(fuse) failure
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Page
6 - 201

Hide quick links:

Advertisement

Table of Contents
loading