ABB REC 561 User Manual page 273

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 171-XEN
Page
5 - 94
6.2 Signal list
6.3 Setting table
PARAMETER:
Operation
I>
t2
Retrip Type
t1
Breaker-failure protection
IN:
BFP--STL1
BFP--STL2
BFP--STL3
BFP--ST3PH
OUT:
BFP--BUTRIP
BFP--RETRIPL1
BFP--RETRIPL2
BFP--RETRIPL3
SETTING RANGE:
Off, On
(10 - 200)% of Ir
(50 - 400) ms
Retrip off, I> Check, No I> Check
(0 - 150) ms
ABB Network Partner AB
DESCRIPTION:
Start breaker-failure phase L1
Start breaker-failure phase L2
Start breaker-failure phase L3
Start breaker-failure three-phase
DESCRIPTION:
Back-up trip
Trip breaker-failure phase L1
Trip breaker-failure phase L2
Trip breaker-failure phase L3
DESCRIPTION:
Activation of the breaker-failure protection
Pick-up current level
Delay timer for back-up trip
Select type of retrip logic
Retrip time delay
Version 1.0-00