ABB REC 561 User Manual page 491

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 151-XEN
Page
6 - 206
6.2.11BH_CONN
Interlocking
Table 20: Output signals for BH_LINE_A
OUT:
ILxx-Q1OPTR
ILxx-Q1CLTR
ILxx-VPQ1TR
Table 21: Input signals for BH_CONN
IN:
IKxx-Q0_OP
IKxx-Q0_CL
IKxx-Q61_OP
IKxx-Q61_CL
IKxx-Q62_OP
IKxx-Q62_CL
IKxx-Q51_OP
IKxx-Q51_CL
IKxx-Q52_OP
IKxx-Q52_CL
IKxx-1Q53_OP
IKxx-1Q53_CL
IKxx-2Q53_OP
IKxx-2Q53_CL
IKxx-Q61EX1
IKxx-Q61EX2
IKxx-Q62EX1
IKxx-Q62EX2
Table 22: Output signals for BH_CONN
OUT:
IKxx-Q0CLREL
IKxx-Q0CLITL
IKxx-Q61REL
IKxx-Q61ITL
IKxx-Q62REL
IKxx-Q62ITL
ABB Network Partner AB
DESCRIPTION:
Signal is 1 if Q1 is open
Signal is 1 if Q1 is closed
Switch status of Q1 is valid (open or closed)
DESCRIPTION:
Signal is 1 if Q0 is open
Signal is 1 if Q0 is closed
Signal is 1 if Q61 is open
Signal is 1 if Q61 is closed
Signal is 1 if Q62 is open
Signal is 1 if Q62 is closed
Signal is 1 if Q51 is open
Signal is 1 if Q51 is closed
Signal is 1 if Q52 is open
Signal is 1 if Q52 is closed
Signal is 1 if Q53 on line 1 is open
Signal is 1 if Q53 on line 1 is closed
Signal is 1 if Q53 on line 2 is open
Signal is 1 if Q53 on line 2 is closed
Input for an external condition for apparatus
Q61
Input for an external condition for apparatus
Q61
Input for an external condition for apparatus
Q62
Input for an external condition for apparatus
Q62
DESCRIPTION:
Closing of Q0 is allowed
Closing of Q0 is forbidden
Switching of Q61 is allowed
Switching of Q61 is forbidden
Switching of Q62 is allowed
Switching of Q62 is forbidden
Version 1.0-00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents