ABB REC 561 User Manual page 501

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 165-XEN
Page
6 - 216
5 Setting
6 Testing
Command function
3. No box active; select the:
• C button to cancel the action and return to the CMD/CDxx menu
window.
• E button to confirm the action and return to the CMD/CDxx menu
window.
• Left arrow to activate the Yes box.
The setting parameters for the Single Command function in REL 531 are
accessible through the SMS.
The setting parameters for the Single Command function and Multiple
Command function in REC 561 are set from the CAP 531 configuration
tool.
Parameters to be set for the Single Command function are MODE, com-
mon for the whole block, and CmdOuty - including the name for each out-
put signal. The MODE input sets the outputs to be one of the types Off ,
Steady, or Pulse.
The Multiple Command function, available in REC 561, has a common
name setting (CmdOut) for the block, MODE as above and INTERVAL
used for the supervision of the cyclical receiving of data.
The appendix shows the parameters and their setting ranges.
For each Single Command function block, it is necessary to configure the
output signal to corresponding binary output of the terminal. The opera-
tion of each separate block is then checked from the built-in MMI by
applying the commands with the MODE Off, Steady, or Pulse and by
observing the logic statuses of the corresponding binary output.
Command function blocks included in the operation of different built-in
functions must be tested at the same time as their corresponding functions.
Test of the Multiple Command function block is recommended to be per-
formed in a system, that is, either in a complete delivery system as an
acceptance test (FAT/SAT) or as parts of that system, because the com-
mand function blocks are connected in a delivery-specific way between
bays and the station level.
ABB Network Partner AB
Version 1.0-00