4.2.6 Built-in MMI

4.2.7 Interlocking

Apparatus control
The high-voltage apparatus can be operated from the built-in MMI via the
SingleCmdFunc block. The SingleCmdFunc block, which must be acces-
sible from the built-in MMI, can be defined from the SMS. The naming of
the signals in the SingleCmdFunc block can be defined from the SMS and
the CAP 531 configuration tool. Fig. 26 shows an example how to con-
nect a SingleCmdFunc block to the apparatus control modules. The com-
mand dialogue from the built-in MMI is performed in two steps, see
"Command function" 1MRK 580 165-XEN.
From BAYCON
SingleCmdFunc
Apparatus 1 open
OUT1
Apparatus 1 close
OUT2
OUT3
OUT4
.
.
OUT16
Defined as pulse outputs
Fig. 26
Connections between a SingleCmdFunc-block controlled from
the built-in MMI and the apparatus control modules
Fig. 27 shows the connection between an interlocking module and appara-
tus control modules. The input is activated when the apparatus is inter-
locked. The interlocking information within the REC 561 control terminal
are taken from the binary input boards. Information from other bays are
transferred over the station bus. The "Reservation function" on page 26
describes the method for transferring these data.
Signals from
.
binary input
.
boards and
.
from other
bays
Fig. 27
Connection of an interlocking module to apparatus control
modules
LOCAL
≥1
Pulse
INPUT OUT
Pulse
INPUT OUT
Pulse length = 1 s
COMCON
OVERRIDE
Interlocking
&
ITL
1MRK 580 150-XEN
Page
6 - 41
Apparatus 1
COMCON
LOCAL
L_SEL_O
L_SEL_C
≥1
L_OPEN
L_CLOSE
(X80150-26)
SWICON
Interlocked
INT_LOCK
(X80150-27)