Version 1.0-00
Interlocking
Table 5: Input signals for AB_TRAFO
IN:
IExx-Q1EX2
IExx-Q1EX3
IExx-Q2EX1
IExx-Q2EX2
IExx-Q2EX3
Table 6: Output signals for AB_TRAFO
OUT:
IExx-Q0CLREL
IExx-Q0CLITL
IExx-Q1REL
IExx-Q1ITL
IExx-Q2REL
IExx-Q2ITL
IExx-Q51REL
IExx-Q51ITL
IExx-Q52REL
IExx-Q52ITL
IExx-Q1OPTR
IExx-Q1CLTR
IExx-Q2OPTR
IExx-Q2CLTR
IExx-Q1Q2OPTR
IExx-Q1Q2CLTR
IExx-VPQ1TR
IExx-VPQ2TR
IExx-VPQ1Q2TR
1MRK 580 151-XEN
DESCRIPTION:
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q2
DESCRIPTION:
Closing of Q0 is allowed
Closing of Q0 is forbidden
Switching of Q1 is allowed
Switching of Q1 is forbidden
Switching of Q2 is allowed
Switching of Q2 is forbidden
Switching of Q51 is allowed
Switching of Q51 is forbidden
Switching of Q52 is allowed
Switching of Q52 is forbidden
Signal is 1 if Q1 is open
Signal is 1 if Q1 is closed
Signal is 1 if Q2 is open
Signal is 1 if Q2 is closed
Signal is 1 if Q1 or Q2 or both are open
Signal is 1 if Q1 and Q2 are closed
Switch status of Q1 is valid (open or closed)
Switch status of Q2 is valid (open or closed)
Switch status of Q1 and Q2 are valid (open
or closed)