ABB REC 561 User Manual page 350

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
7.2.2 BAYCONB
Apparatus control
Table 3: Input signals for BAYCONB
IN:
BBxx-S_R
BBxx-S_S
BBxx-L_L
BBxx-EXCH_IN
BBxx-RQ_SEL1
BBxx-RQ_SEL2
BBxx-RQ_SEL3
BBxx-RQ_SEL4
BBxx-RQ_SEL5
BBxx-RQ_SEL6
BBxx-RQ_SEL7
BBxx-RQ_SEL8
BBxx-BLK_RE
BBxx-OVERRIDE
BBxx-RE_B1
BBxx-RE_B2
BBxx-RE_B3
BBxx-RE_B4
BBxx-RE_B5
BBxx-RE_B6
BBxx-RE_B7
BBxx-RE_B8
1MRK 580 150-XEN
DESCRIPTION:
Input to change operator place to Remote
(pulse input)
Input to change operator place to Station
(pulse input)
Input to change operator place to Local
Input for information exchange with other
BAYCON:s in bays with more than 8 appa-
ratuses
Request for selection and reservation of
apparatus 1
Request for selection and reservation of
apparatus 2
Request for selection and reservation of
apparatus 3
Request for selection and reservation of
apparatus 4
Request for selection and reservation of
apparatus 5
Request for selection and reservation of
apparatus 6
Request for selection and reservation of
apparatus 7
Request for selection and reservation of
apparatus 8
Input for blocking all reservations
Input for overriding the reservation function
including the blocking by BLK_RE
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 1
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 2
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 3
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 4
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 5
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 6
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 7
Reservation of the own bay only (i.e. not
other bays) at selection from apparatus 8
Page
6 - 65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents