7.2.9 SWICONB
Apparatus control
Table 17: Input signals for SWICONB
IN:
SBxx-POSIND_V
SBxx-POS_L1_O
SBxx-POS_L2_O
SBxx-POS_L3_O
SBxx-POS_L1_C
SBxx-POS_L2_C
SBxx-POS_L3_C
SBxx-BLK_UPD
SBxx-PROC_UPD
SBxx-MA_UPD_O
SBxx-MA_UPD_C
SBxx-UPD_BLK
SBxx-SELECT
SBxx-FDB_SEL
SBxx-OPEN
SBxx-CLOSE
SBxx-AU_OP_V
SBxx-EXECUTE
SBxx-CANCEL
SBxx-BLK_OPEN
SBxx-BLK_CLOS
SBxx-INT_LOCK
1MRK 580 150-XEN
DESCRIPTION:
Input for external position check function,
i.e. valid position of the apparatus
Input for open position indication in phase
L1
Input for open position indication in phase
L2
Input for open position indication in phase
L3
Input for close position indication in phase
L1
Input for close position indication in phase
L2
Input for close position indication in phase
L3
Blocking of updating of the position indica-
tion (pulse input from COMCON)
Resuming of updating of the position indica-
tion (pulse input from COMCON)
Input for manual setting of open position
(pulse input from COMCON)
Input for manual setting of close position
(pulse input from COMCON)
Input for blocking of updating (from BLK-
CONK at blocking of all apparatuses in a
bay)
Selection input (from BAYCON, signal
SELx)
Feedback selection input
Open direction for operation (pulse input
from COMCON)
Close direction for operation (pulse input
from COMCON)
Automatic operation permitted (signal from
BAYCON)
Execution of operation (pulse input from
COMCON)
Cancelling of the selected operation (pulse
input from COMCON)
Blocking input for open direction
Blocking input for close direction
Operation blocked by conditions from the
interlocking module