ABB REC 561 User Manual page 473

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 151-XEN
Page
6 - 188
6.2 Signal list
6.2.1 ABC_LINE
Interlocking
Table 1: Input signals for ABC_LINE
IN:
IFxx-Q0_OP
IFxx-Q0_CL
IFxx-Q9_OP
IFxx-Q9_CL
IFxx-Q1_OP
IFxx-Q1_CL
IFxx-Q2_OP
IFxx-Q2_CL
IFxx-Q7_OP
IFxx-Q7_CL
IFxx-Q51_OP
IFxx-Q51_CL
IFxx-Q52_OP
IFxx-Q52_CL
IFxx-Q8_OP
IFxx-Q8_CL
IFxx-Q15_OP
IFxx-Q15_CL
IFxx-Q25_OP
IFxx-Q25_CL
IFxx-Q75_OP
IFxx-Q75_CL
IFxx-C_DC_OP
IFxx-BC_AB_CL
IFxx-BC_AC_OP
IFxx-BC_AC_CL
IFxx-BC_BC_OP
IFxx-BC_BC_CL
IFxx-VOLT_OP
IFxx-VOLT_CL
ABB Network Partner AB
DESCRIPTION:
Signal is 1 if Q0 is open
Signal is 1 if Q0 is closed
Signal is 1 if Q9 is open
Signal is 1 if Q9 is closed
Signal is 1 if Q1 is open
Signal is 1 if Q1 is closed
Signal is 1 if Q2 is open
Signal is 1 if Q2 is closed
Signal is 1 if Q7 is open
Signal is 1 if Q7 is closed
Signal is 1 if Q51 is open
Signal is 1 if Q51 is closed
Signal is 1 if Q52 is open
Signal is 1 if Q52 is closed
Signal is 1 if Q8 is open
Signal is 1 if Q8 is closed
Signal is 1 if Q15 on busbar A is open
Signal is 1 if Q15 on busbar A is closed
Signal is 1 if Q25 on busbar B is open
Signal is 1 if Q25 on busbar B is closed
Signal is 1 if Q75 on busbar C is open
Signal is 1 if Q75 on busbar C is closed
All line disconnectors on bypass busbar C
except in the own bay are open
There exists a bus coupler connection
between busbar A and B
There is no bus coupler connection
between busbar A and C
There exists a bus coupler connection
between busbar A and C
There is no bus coupler connection
between busbar B and C
There exists a bus coupler connection
between busbar B and C
There is no voltage on the line and not fuse
failure
There is voltage on the line or there is a VT
(fuse) failure