ABB REC 561 User Manual page 583

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 133-XEN
Page
7 - 64
PARAMETER:
IndicationMask
Analog/U1 - U5:
Operation
Trig U>
U>
Trig U<
U<
Analog/I1 - I5:
Operation
Trig I>
I>
Trig I<
I<
ServiceReport/DisturbReport/SequenceNo:
SequenceNo
Disturbance report - Settings
SETTING RANGE:
Masked, Show
Off, On
Off, On
(0 - 200)% of Ur/sqr3
Off, On
( 0 - 110)% of Ur/sqr3
Off, On
Off, On
(0 - 5000)% of Ir
Off, On
(0 - 200)% of Ir
(0-255)
DESCRIPTION:
Masked=the signal is not automatically
scrolled,
Show=the signal is automatically scrolled on
the MMI in the Disturbance summary
On=the signal is recorded in the Distur-
bance recorder
Off=the signal is not recorded
Over trig operation
Over trig value
Under trig operation
Under trig value
On=the signal is recorded in the Distur-
bance recorder
Over trig operation
Over trig value
Under trig operation
Under trig value
Sequence no. of the disturbance
ABB Network Partner AB
Version 1.0-00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents