Apparatus control
Table 5: Input signals for BAYCONC
IN:
BCxx-V_TX
BCxx-EX_DA_UP
BCxx-RE_RQ_B
BCxx-V_RE_RQ
BCxx-SEL_ACT1
BCxx-SEL_ACT2
BCxx-SEL_ACT3
BCxx-SEL_ACT4
BCxx-SEL_ACT5
BCxx-SEL_ACT6
BCxx-SEL_ACT7
BCxx-SEL_ACT8
BCxx-SEL_CH1
BCxx-SEL_CH2
BCxx-INPBOERR
BCxx-OUTBOERR
Table 6: Output signals for BAYCONC
OUT:
BCxx-REMOTE
BCxx-STATION
BCxx-LOCAL
1MRK 580 150-XEN
DESCRIPTION:
Indication for valid transmission of the reser-
vation signals
Input is 1 if the program that acknowledged
the reservation is running
Request for reservation from other bays
Input is 1 for valid request of reservation
from any bay
Selection of apparatus 1 is activated by the
program and the selection relay should be
energized
Selection of apparatus 2 is activated by the
program and the selection relay should be
energized
Selection of apparatus 3 is activated by the
program and the selection relay should be
energized
Selection of apparatus 4 is activated by the
program and the selection relay should be
energized
Selection of apparatus 5 is activated by the
program and the selection relay should be
energized
Selection of apparatus 6 is activated by the
program and the selection relay should be
energized
Selection of apparatus 7 is activated by the
program and the selection relay should be
energized
Selection of apparatus 8 is activated by the
program and the selection relay should be
energized
Indication that no selection or execution
relay is energized
Indication that at least one selection or exe-
cution relay is energized
Input for binary input board error
Input for binary output board error
DESCRIPTION:
Indication of Remote operator place
Indication of Station operator place
Indication of Local operator place