ABB REC 561 User Manual page 481

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 151-XEN
Page
6 - 196
6.2.4 A1A2_BS
Interlocking
Table 7: Input signals for A1A2_BS
IN:
IHxx-Q0_OP
IHxx-Q0_CL
IHxx-Q11_OP
IHxx-Q11_CL
IHxx-Q12_OP
IHxx-Q12_CL
IHxx-Q51_OP
IHxx-Q51_CL
IHxx-Q52_OP
IHxx-Q52_CL
IHxx-A1Q15_OP
IHxx-A1Q15_CL
IHxx-A2Q15_OP
IHxx-A2Q15_CL
IHxx-BBTR_OP
IHxx-VP_BBTR
IHxx-EXDUP_AB
IHxx-EXVVA_AB
IHxx-EXDUP_ES
IHxx-EXVVA_ES
IHxx-Q0_O_EX1
IHxx-Q0_O_EX2
IHxx-Q0_O_EX3
IHxx-Q11EX1
IHxx-Q11EX2
IHxx-Q12EX1
IHxx-Q12EX2
ABB Network Partner AB
DESCRIPTION:
Signal is 1 if Q0 is open
Signal is 1 if Q0 is closed
Signal is 1 if Q11 is open
Signal is 1 if Q11 is closed
Signal is 1 if Q12 is open
Signal is 1 if Q12 is closed
Signal is 1 if Q51 is open
Signal is 1 if Q51 is closed
Signal is 1 if Q52 is open
Signal is 1 if Q52 is closed
Signal is 1 if Q15 on busbar A1 is open
Signal is 1 if Q15 on busbar A1 is closed
Signal is 1 if Q15 on busbar A2 is open
Signal is 1 if Q15 on busbar A2 is closed
Signal is 1 if no busbar transfer is in
progress concerning this bus section
Switch status are valid for all apparatuses
involved in the busbar transfer
Signal is 1 if there is no transmission error
from any bay connected to the AB busbars
Signal is 1 if the interlocking programs in all
bays connected to the AB busbars are run-
ning
Signal is 1 if there is no transmission error
from any bay containing earthing switches
Q15 in section A1 and A2
Signal is 1 if the interlocking programs in all
bays containing earthing switches Q15 in
section A1 and A2 are running
Input for an external open condition for
apparatus Q0
Input for an external open condition for
apparatus Q0
Input for an external open condition for
apparatus Q0
Input for an external condition for apparatus
Q11
Input for an external condition for apparatus
Q11
Input for an external condition for apparatus
Q12
Input for an external condition for apparatus
Q12
Version 1.0-00