ABB REC 561 User Manual page 474

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
Interlocking
Table 1: Input signals for ABC_LINE
IN:
IFxx-VP_C_DC
IFxx-VP_BC_AB
IFxx-VP_BC_AC
IFxx-VP_BC_BC
IFxx-EXDUP_ES
IFxx-EXVVA_ES
IFxx-EXDU_BPB
IFxx-EXVV_BPB
IFxx-EXDUP_BC
IFxx-EXVVA_BC
IFxx-Q9EX1
IFxx-Q9EX2
IFxx-Q1EX1
IFxx-Q1EX2
IFxx-Q1EX3
IFxx-Q2EX1
IFxx-Q2EX2
IFxx-Q2EX3
IFxx-Q7EX1
IFxx-Q7EX2
1MRK 580 151-XEN
DESCRIPTION:
Switch status of the disconnectors on
bypass busbar C are valid (open or closed)
Switch status of the bus coupler appara-
tuses connected between busbar A and B
are valid (open or closed)
Switch status of the bus coupler appara-
tuses connected between busbar A and C
are valid (open or closed)
Switch status of the bus coupler appara-
tuses connected between busbar B and C
are valid (open or closed)
Signal is 1 if there is no transmission error
from any bay containing earthing switches
Q15, Q25 or Q75
Signal is 1 if the interlocking programs in all
bays containing earthing switches Q15, Q25
or Q75 are running
Signal is 1 if there is no transmission error
from any bay containing disconnectors on
bypass busbar C
Signal is 1 if the interlocking programs in all
bays containing disconnectors on bypass
busbar C are running
Signal is 1 if there is no transmission error
from any bus coupler bay
Signal is 1 if the interlocking programs in all
bus coupler bays are running
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q9
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q7
Input for an external condition for apparatus
Q7
Page
6 - 189