Setting Table - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 120-XEN
Page
5 - 8
IN:
DESCRIPTION:
TRIP-PSL3
Necessary condition for single phase trip in phase L3. Generally connected to protective
functions with phase selective operation
TRIP-PTPTRIP
Turns the tripping logic into three phase operating mode.
TRIP-TRSPZ
Initiation of single phase tripping. Requires a phase selection signal. In opposite case initi-
ate 50 ms delayed three phase tripping.
TRIP-TRTP
Initiation of three phase tripping.
OUT:
DESCRIPTION:
TRIP-GTRIP
General information on tripping caused by tripping logic within the terminal.
TRIP-SPTRIP
General information on single phase tripping caused by tripping logic within the terminal
TRIP-TPTRIP
General information on three phase tripping caused by tripping logic within the terminal
TRIP-TRIPL1
Trip in phase L1
TRIP-TRIPL2
Trip in phase L2
TRIP-TRIPL3
Trip in phase L3

4.3 Setting table

PARAMETER:
SETTING RANGE:
Operation
Off, 3ph, 1ph
Tripping logic
DESCRIPTION
Operating mode of the tripping logic.
Off: the operation is disabled.
3ph: only three phase tripping is possible.
1ph: single phase or three phase tripping, dependent on combina-
tion of different input signals
ABB Network Partner AB
Version 1.0-00